Modbus master command set, Modbus data types and addressing -4, Configuration guide (aadvance controller) – Rockwell Automation AADvance Controller Configuration Guide User Manual
Page 190: Modbus data types and addressing
9-4
Document: 553633
ICSTT-RM405f-EN-P
Issue 07
Configuration Guide (AADvance Controller)
Modbus Master Command Set
The AADvance Modbus master supports the subset of Modbus commands listed in the
table.
Table 20:
AADvance Modbus Master Commands
Command
Code
Command
Remarks
01
Read coil status
Maximum 512 coils per message
02
Read input status
Maximum 512 inputs per message
03
Read holding registers
Maximum 125 registers per message
04
Read input registers
Maximum 125 registers per message
05
Force single coil
06
Preset single register
15
Write multiple coils
Maximum 512 coils per message
16
Write holding registers
Maximum 123 registers per message
08
Diagnostics
Subfunction 00, query used (RTU only)
Modbus Data Types and Addressing
The Modbus master supports the Modbus data types listed in the table.
Table 21:
Modbus Data Types
Data Type
Address Range
Coils
1 to 65,535
Inputs
1 to 65,535
Input registers
1 to 65,535
Holding registers
1 to 65,535
Modbus uses a numeric addressing scheme to pass data between devices. AADvance
controllers allocate a dedicated area for each of the four Modbus data types and follow
the model defined in the Modbus Application Protocol Specification.