Rockwell Automation AADvance Controller Configuration Guide User Manual
Page 37
Document: 553633
ICSTT-RM405f-EN-P
Issue 07
3-5
8) Refresh the screen to confirm that the new resource number is displayed in the
resource field and the controller status is configurable.
The Resource Number must also be configured in the application, in the
Resource Properties.
Configure the IP Address in the Controller
When you build a new AADvance controller, or install a new 9100 processor base
unit, you have to configure the IP Address stored in the controller.
The procedure to configure the IP Address uses the AADvanceDiscover utility.
Changes take effect immediately and you do not have to restart the controller. To set
the IP Address do the following:
1) Make a note of the controller's MAC address (Controller ID); this is shown on a
label on the processor base unit. Install at least one 9110 processor module into
the processor base unit.
2) Make sure the program enable key is inserted in the KEY connector on the
processor base unit.
3) Start the AADvanceDiscover tool from the Start menu:
Start
All Programs
AADvance
AADvance Discover.
The AADvanceDiscover utility scans the network for controllers, and
creates a list.
4) Locate the controller in the list and make sure that the status of the controller is
Configurable.
5) Double-click on the MAC address in the Controller ID field.
The resource and IP address dialog box opens.