Rockwell Automation AADvance Controller Configuration Guide User Manual
Page 81
Document: 553633
ICSTT-RM405f-EN-P
Issue 07
4-41
FALSE = No fault reset button is active.
Default: FALSE
Description:
Reports that the fault reset button on any processor module has been pressed. The
system health reset is triggered by pressing the button, but the value does not change
to TRUE until the beginning of the next application cycle. The value remains TRUE for
the duration of the cycle and then reverts to FALSE, even if the button has been held
down throughout.
Dongle Detected (Voted)
Direction: input to application from controller
Type: boolean
Values:
TRUE = One or more 9110 processor modules is detecting the presence of a
program enable key at the KEY connector on the 9100 processor base unit.
FALSE = No processor module can detect the presence of a program enable key.
Description:
Reports the presence or absence of a program enable key.
Processor Module A On-line
Direction: input to application from controller
Type: boolean
Values:
TRUE = The 9110 processor module in the given slot is on-line
FALSE = The processor module is off-line
Default: TRUE
Description:
Reports that a processor module within a dual or triple modular redundant
configuration is present and is communicating through the inter-processor link to one
or both of its peers. Reports that a simplex processor module is present.