Configuration Guide (AADvance Controller)
T9K_DI_COMPACT and T9K_DI_FULL (Digital Inputs)
The two data structures for digital input channels (T9K_DI_COMPACT and
T9K_DI_FULL) provide the elements detailed in the tables.
Table 6:
T9K_DI_COMPACT Structure for Digital Inputs
Identifier
Type
Description
Remarks
BOOL
Input state
TRUE: input voltage above threshold T6
FALSE: input voltage below threshold T5
BOOL
Line fault
TRUE: input voltage above threshold T8;
between T5 and T4; or below T1
FALSE: input voltage between thresholds T2
and T3; or between T6 and T7
BOOL
Discrepancy
TRUE: there is a discrepancy in voltage greater
than 20% between the channels of two or
three modules in a redundant configuration (†)
Table 7:
T9K_DI_FULL Structure for Digital Inputs
Identifier
Type
Description
Remarks
BOOL
Input state
TRUE: input voltage above threshold T6
FALSE: input voltage below threshold T5
BOOL
Line fault
TRUE: input voltage above threshold T8;
between T5 and T4; or below T1
FALSE: input voltage between thresholds T2
and T3; or between T6 and T7
BOOL
Discrepancy
TRUE: there is a discrepancy in voltage greater
than 8% (of 24V) between the channels of two
or three modules in a redundant configuration
(†)
BOOL
Channel fault
TRUE: module diagnostics detect a fault in the
channel electronics or firmware (state = 7)
UINT
Voltage
Reports the channel voltage in units of
millivolts and with an accuracy of ± 500mV
(††)