beautypg.com

Rockwell Automation AADvance Controller Configuration Guide User Manual

Page 80

background image

4-40

Document: 553633
ICSTT-RM405f-EN-P

Issue 07

Configuration Guide (AADvance Controller)


Control Integers

The variables in the rack of control integers enable the application to send specific
information to the controller.

AUX LED Colour

Direction: output from application to controller
Type: word
Values:

0..3 (0 = off, 1 = red, 2 = green, 3 = amber)

Default 0

Description:
Sets the state of the LED indicator labelled 'Aux' on every 9110 processor module.

Status Booleans

The variables in the rack of status booleans provide information about the controller
to the application.

System Health

Direction: Input to application from controller
Type: BOOLEAN
Values:

TRUE = All installed processor and I/O modules are healthy and System Health

variable is FALSE (See Control Booleans). The processor module System

Healthy LED is green.

FALSE = One or more of the installed processors and/or I/O modules are
reporting a module health problem or the System Health variable is TRUE (See

Control Booleans). The processor module System Healthy LED is red.

Note: If there is at least 1 healthy processor or I/O module in a module group then
the System Health alarm can be reset after a fault.

System Health Reset (Voted 1oo3)

Direction: input to application from controller
Type: boolean
Values:

TRUE = The fault reset button on any 9110 processor module has been pressed;

valid for one scan only.