Rockwell Automation AADvance Controller Configuration Guide User Manual
Page 80
4-40
Document: 553633
ICSTT-RM405f-EN-P
Issue 07
Configuration Guide (AADvance Controller)
Control Integers
The variables in the rack of control integers enable the application to send specific
information to the controller.
AUX LED Colour
Direction: output from application to controller
Type: word
Values:
0..3 (0 = off, 1 = red, 2 = green, 3 = amber)
Default 0
Description:
Sets the state of the LED indicator labelled 'Aux' on every 9110 processor module.
Status Booleans
The variables in the rack of status booleans provide information about the controller
to the application.
System Health
Direction: Input to application from controller
Type: BOOLEAN
Values:
TRUE = All installed processor and I/O modules are healthy and System Health
variable is FALSE (See Control Booleans). The processor module System
Healthy LED is green.
FALSE = One or more of the installed processors and/or I/O modules are
reporting a module health problem or the System Health variable is TRUE (See
Control Booleans). The processor module System Healthy LED is red.
Note: If there is at least 1 healthy processor or I/O module in a module group then
the System Health alarm can be reset after a fault.
System Health Reset (Voted 1oo3)
Direction: input to application from controller
Type: boolean
Values:
TRUE = The fault reset button on any 9110 processor module has been pressed;
valid for one scan only.