Configuration Worksheets
Shown below is the Sequencer Mode Configuration Worksheet for the
Output and M0 File. A blank worksheet is supplied in Appendix E.
Direct Outputs (page 4-36)
Output Source Select (page 4-24)
Setup and Control Word (page 4-25)
0
0
0
0
0
0
0
0
R
R
R
R
R
R
R
R
O:e.0
Direct Outputs
1 = output ON if under processor control
7
6
5
4
3
2
1
0
7
6
5
4
3
2
1
0
Bit Number (decimal)
Output Number
15
14
13
12
11
10
9
8
Bits 0 thru 3 relate to Physical Outputs
Bits 4 thru 7 relate to Soft Outputs
M0:e.0
7
6
5
4
3
2
1
0
Bit Number (decimal)
15
14
13
12
11
10
9
8
1 = processor 0 = Module
Output Source Select
R
R
R
R
R
R
R
R
Bits 0 thru 3 relate to Physical Outputs
Bits 4 thru 7 relate to Soft Outputs
R
= Reserved, must be reset to 0
0
0
0
1
0
0
0
0
ATTENTION
The module will fault on power-up if you do not
enter a value.
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
10 = Sequencer
0 = Linear
1 = Ring
0 = Disable counter
1 = Enable counter
0 = Increment
1 = Decrement
Setup and Control Word
M0:e.1
Bit Number (decimal)
000 = No reset
001 = Z
010 = LS
011 = LS and Z
100 = SR
101 = SR and Z
110 = SR and LS
111 = SR, LS, and Z
0 = False
1 = True
1 = Hold
0 = Outputs OFF
1 = Outputs enabled
0 = No change
1 = Sequencer reset
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
R
000 = Invalid
001 = Invalid
010 = Pulse & Direction/External Control
011 = Pulse & Direction/Internal Control
100 = Quadrature Encoder x1
101 = Quadrature Encoder x2
110 = Quadrature Encoder x4
111 = Up / Down Pulse Inputs
Counter Type (page 4-31) Function Control (page 4-30)
Soft Reset (page 4-27)
Sequencer Reset (page 4-26)
Operating Mode (page 4-31)
Input Type (page 4-29)
Reset Mode (page 4-28)
Up/Down Count Direction (page 4-27)
Enable Outputs (page 4-26)
Counter Hold (page 4-27)