I:e.3 rate measurement (hz), I:e.4 output status, configuration error code, I:e.4 bits 0 through 7 - configuration error code – Rockwell Automation 1746-HSCE,D17466.5 High-Speed Counter Module User Manual
Page 103

Publication 1746-UM006B-EN-P - August 2005
Configuration and Programming 4-43
I:e.3 Rate Measurement (Hz)
This word indicates the current rate at which the count is being
received (in Hz). This value is updated after every Rate Period.
This input value is active in all modes. When the module is used with
encoders and configured for x2 or x4 input types, the calculated value
will be scaled down by a factor or two or four respectively.
I:e.4 Output Status, Configuration Error Code
I:e.4 Bits 0 through 7 - Configuration Error Code
Bit Number (decimal)
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
Rate Measurement Word 3
I:e.3
Bit Number (decimal)
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
Output Status and Configuration Error Code, Word 4
I:e.4
Physical Outputs 0–3
Configuration Error Code
Soft Outputs 4–7
Configuration
Error Code
Reason
Critical
Error
Action
Hex Binary
01
0000 0001 not defined
-
reconfigure
(1)
(1) The Function Control bit must be reset to 0, the parameter must be changed, and the Function Control bit is
then set to 1
.
02
0000 0010 max count = 0 (ring)
yes
reconfigure
03
0000 0011 invalid operating mode
yes
reconfigure
04
0000 0100 invalid input type
yes
reconfigure
05
0000 0101 static parameter changed
yes
reconfigure
06
0000 0110 ranges active = 0
no
change parameter
07
0000 0111 rate period = 0
no
change parameter
08
0000 1000 linear counter reset value out of range
no
change parameter
09
0000 1001 sequencer preset > max. count
no
change parameter