Chapter
5
Start-Up, Operation, and Troubleshooting
This chapter provides start-up, operation, troubleshooting, and error
handling information.
Start-Up
The following steps will assist you in the start up of your module.
1. Install the module in your SLC chassis.
2. Wire the input and output devices as discussed in Chapter 3.
3. Configure and program your SLC processor to operate with the
module as discussed in Chapter 4.
4. Apply power to the SLC system and the attached input and
output devices.
When power is applied to the SLC system, the SLC processor and
module run through a power up diagnostic sequence. After the
diagnostics are successfully completed, the SLC processor enters run
mode and normal operation begins.
If the SLC processor was in the program (or test) mode when power
was removed, it will return to the program (or test) mode when
power is reapplied. Place the SLC processor into run mode using an
SLC programming device.
Normal Operation
During normal operation, the LEDs are illuminated as follows:
•
The FAULT LED will be off.
•
LEDs A, B, Z, and LS illuminate indicating the input is energized.
•
LEDs 0, 1, 2, and 3 illuminate indicating the Physical Output
status.
•
LEDs 4, 5, 6, and 7 illuminate indicating the Soft Output status.