Getting Started

1-5

In Multi-Drive mode, any channel can be configured for “RTU Master”
operation (

Figure 1.4

). This enables connection of up to 31 RTU Slave

devices, such as PowerFlex 7-Class drives with 20-COMM-H RS485
HVAC adapters.

Figure 1.4 Multi-Drive Mode and Modbus RTU Master Mode Wiring Example

120 ohm, ¼ Watt

Terminating Resistor

AK-U0-RJ45-TB2P

Terminal Block

Connectors

AK-U0-RJ45-TB2P

Terminal Block

Connectors

MODULE

CH1

CH2

CH3

C

H

1

C

H

2

C

H

3

1769-SM2

Module

CH3 - Modbus RTU Master Mode (up to 31 Devices)

CH1 - Multi-Drive Mode (up to 5 PowerFlex 4-Class Drives)

CH2 - Multi-Drive Mode (up to 5 PowerFlex 4-Class Drives)

120 ohm, ¼ Watt

Terminating Resistor

120 ohm, ¼ Watt

Terminating Resistor

CH1
CH2
CH3

User-Supplied Wire (recommend
Belden No. 3105A or equivalent)

User-Supplied Wire (recommend
Belden No. 3105A or equivalent)

User-Supplied Wire (recommend
Belden No. 3105A or equivalent)

Ground Wire Connection

(for network

communication

cable shielding)

Earth Ground
Connection

PowerFlex 7-Class Drives

with 20-COMM-H RS485 HVAC

Communication Adapters

Generic

Modbus RTU

Device

. . .

Wiring Tip:
The 1769-SM2 has an
integral terminating
resistor for each channel.
Thus, it is only necessary
to connect a terminating
resistor to the RJ45
terminal block at the last
drive on each channel.