Specifications A-5
Surge current per point:
•
peak current
•
maximum surge duration
•
maximum rate of repetition at 30 °C (86 °F)
•
maximum rate of repetition at 55 °C (131 °F)
•
4.0A
•
10 ms
•
once every second
•
once every 2 seconds
•
Not applicable
•
Not applicable
•
Not applicable
•
Not applicable
Turn-on time, max.
0.1 ms
6 µs
Turn-off time, max.
1.0 ms
18 µs
Repeatability, max.
n/a
2 µs
Drift, max.
n/a
1 µs per 5 °C (41 °F)
(1) Output 2 is designed to provide increased functionality over the other FET outputs. Output 2 may be used like the other FET transistor outputs, but in addition, within a
limited current range, it may be operated at a higher speed. Output 2 also provides a pulse train output (PTO) or pulse width modulation output (PWM) function.
Table A.4 BXB FET Output Specifications
Attribute
General Operation
High Speed Operation
(1)
(Output 2 Only)
Table A.5 AC Input Filter Settings
Nominal Filter Setting (ms)
ON Delay (ms)
OFF Delay (ms)
Minimum Maximum
Minimum Maximum
8 2
20
10
20
Table A.6 Fast DC Input Filter Settings (Inputs 0 to 3)
Nominal Filter Setting (ms)
ON Delay (ms)
OFF Delay (ms)
Maximum Counter Frequency (Hz)
50% Duty Cycle
Minimum Maximum
Minimum Maximum
0.025
0.005
0.025
0.005
0.025
20.0 kHz
0.075
0.040
0.075
0.045
0.075
6.7 kHz
0.100
0.050
0.100
0.060
0.100
5.0 kHz
0.250
0.170
0.250
0.210
0.250
2.0 kHz
0.500
0.370
0.500
0.330
0.500
1.0 kHz
1.00
0.700
1.000
0.800
1.000
0.5 kHz
2.000
1.700
2.000
1.600
2.000
250 Hz
4.000
3.400
4.000
3.600
4.000
125 Hz
8.000
(1)
6.700
8.000
7.300
8.000
63 Hz
16.000
14.000
16.000
14.000
16.000
31 Hz