Mount the controller, Mount the controller -14 – Rockwell Automation 1762-Lxxxx MicroLogix 1200 Programmable Controllers User Manual
Page 28

Publication 1762-UM001G-EN-P - March 2011
2-14 Install Your Controller
Mount the Controller
MicroLogix 1200 controllers are suitable for use in an industrial environment
when installed in accordance with these instructions. Specifically, this
equipment is intended for use in clean, dry environments (Pollution degree
2
(1)
) and to circuits not exceeding Over Voltage Category II
(2)
(IEC
60664-1).
(3)
(1) Pollution Degree 2 is an environment where, normally, only non-conductive pollution occurs except that
occasionally a temporary conductivity caused by condensation shall be expected.
(2) Over Voltage Category II is the load level section of the electrical distribution system. At this level transient
voltages are controlled and do not exceed the impulse voltage capability of the product’s insulation.
(3) Pollution Degree 2 and Over Voltage Category II are International Electrotechnical Commission (IEC)
designations.
ATTENTION
Do not remove the protective debris shield until after
the controller and all other equipment in the panel
near the controller are mounted and wiring is
complete. Once wiring is complete, remove
protective debris shield. Failure to remove shield
before operating can cause overheating.
ATTENTION
Electrostatic discharge can damage semiconductor
devices inside the controller. Do not touch the
connector pins or other sensitive areas.
TIP
For environments with greater vibration and shock
concerns, use the panel mounting method described
on page 2-16, rather than DIN rail mounting.
debris shield