beautypg.com

Rockwell Automation 1762-Lxxxx MicroLogix 1200 Programmable Controllers User Manual

Page 38

background image

Publication 1762-UM001G-EN-P - March 2011

3-4 Wire Your Controller

The following diagram shows an output with a suppression device. We
recommend that you locate the suppression device as close as possible to the
load device.

If the outputs are dc, we recommend that you use an 1N4004 diode for surge
suppression, as shown below. For inductive dc load devices, a diode is suitable.
A 1N4004 diode is acceptable for most applications. A surge suppressor can
also be used. See Table 3.2 for recommended suppressors. As shown below,
these surge suppression circuits connect directly across the load device.

Suitable surge suppression methods for inductive ac load devices include a
varistor, an RC network, or an Allen-Bradley surge suppressor, all shown
below. These components must be appropriately rated to suppress the
switching transient characteristic of the particular inductive device. See the
table on page 3-5 for recommended suppressors.

+dc or L1

Suppression
Device

dc COM or L2

ac or dc
Outputs

Load

VAC/DC

Out 0
Out 1

Out 2

Out 3

Out 4

Out 5
Out 6

Out 7

COM

+24V dc

IN4004 Diode

Relay or Solid
State dc Outputs

24V dc common

VAC/DC

Out 0
Out 1
Out 2
Out 3
Out 4
Out 5
Out 6
Out 7

COM

(A surge suppressor
can also be used.)

Surge Suppression for Inductive ac Load Devices

Output Device

Output Device

Output Device

Varistor

RC Network

Surge
Suppressor

This manual is related to the following products: