Rockwell Automation 1762-Lxxxx MicroLogix 1200 Programmable Controllers User Manual
Page 117

Publication 1762-UM001G-EN-P - March 2011
Specifications A-25
Vendor ID code
1
Product type code
7
Product code
98
Table A.32 DC-Input/Relay-Output Combination Module - 1762-IQ80W6
Environmental Specifications
Specification
Value
Temperature range, operating
-20…+65 °C (-4…+149 °F)
Temperature range, storage
-40…+85 °C (-40…+185 °F)
Operating humidity
5…95% non-condensing
Operating altitude
2000 m (6561 ft)
Table A.33 Certifications
Certification
Value
Agency certification
C-UL certified (under CSA C22.2 No. 142)
UL 508 listed
CE compliant for all applicable directives
Hazardous environment class
Class I, Division 2, Hazardous Location,
Groups A, B, C, D (UL 1604, C-UL under
CSA C22.2 No. 213)
Radiated and conducted emissions
EN50081-2 Class A
Electrical/EMC:
The module has passed testing at the
following levels:
ESD immunity (IEC1000-4-2)
4 kV contact, 8 kV air, 4 kV indirect
Radiated RF immunity
(IEC1000-4-3)
10 V/m, 80…1000 MHz, 80% amplitude
modulation, +900 MHz keyed carrier
EFT/B immunity (IEC1000-4-4)
2 kV, 5 kHz
Surge transient immunity
(IEC1000-4-5)
2 kV common mode, 1 kV differential
mode
Conducted RF immunity
(IEC1000-4-6)
10V, 0.15…80 MHz
(1)
(1) Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency
range is 30…1000 MHz.
Table A.31 DC-Input/Relay-Output Combination Module - 1762-IQ80W6 General
Specifications
Specification
Value