beautypg.com

Rockwell Automation 1336T ControlNet Frn1.02 Rev 1.5 User Manual

Page 48

background image

4–6

Using Unscheduled Messaging

Publication 1336 FORCE–5.18 ––March, 1999

Rung 2:2
This rung will read parameters 100-109 on a continuous basis by using the Message Block enable bit to toggle the next message.
The parameter information is stored in N20:0–9 in the PLC.
The drive ControlNet address is 15.

Message Block Contents

This PLC–5

(EN)

(DN)

(ER)

EN

Message Enable Bit

Drive 15

MG9:1

Drive 15
Parameter Read

MSG

Read/Write Message

Control MG9:1

: PLC–5 Typed Read
: N20:0
: 10
: 2

Communication Command

Data Table Address

Size in Elements

Port Number

: N10:100
: 15

Data Table Address

ControlNet Path

Target Device

0002

Setup Screen

MSG MG9:1

X

This PLC–5

Communication Command:

Data Table Address:

Size in Elements:

Port Number:

PLC–5 Typed Read

N20:0

10

2

Target Device

Data Table Address:

ControlNet Path:

N10:100

15

Control Bits

Ignore if timed out (TO):

To be retired(NR):

0

0

Awaiting Execution(EW):

0

0

0

Continuous Run(EW):

Error(ER):

0

Message done(DN):

0

Message enabled(EN):

Enable

Error Code (Hex): 0

EXAMPLE 2