Parameters

Publication 1336 FORCE–5.18 ––March, 1999

489

Trend 4 Post Samples

[Tr4 Post Samples]

Tr4 Post Samples specifies the number of data
samples to be gathered once the trigger evaluation
becomes true. There is always a sample reserved
for the instance when the trigger condition becomes
true.

Parameter Number

489

Parameter Type

Read/Write, Non–Linkable Sink

Display Units / Drive Units

None

Factory Default

15

Minimum Value

0

Maximum Value

499

File – Group

Diagnostics – Trend Setup

490

Trend 4 Continuous Trigger

[Tr4 Cont Trigger]

Tr4 Cont Trigger specifies the type of trend. You can
choose either 0 for one–shot or 1 for continuous.

With a one–shot trend, once the trigger condition is
true and the number of samples after the trigger is
taken are gathered, the trend stops.

With a continuous trend, once the trigger condition is
true and the number of samples after the trigger is
taken are gathered, the trend continues looking for
the next occurrence of a true trigger condition.

Parameter Number

490

Parameter Type

Read/Write, Non–Linkable Sink

Display Units / Drive Units

None

Factory Default

0

Minimum Value

0

Maximum Value

1

File – Group

Diagnostics – Trend Setup

491

Trend 4 Select

[Tr4 Select]

Tr4 Select specifies the trend mode. The states are
as follows:

0

Disable the trend.

1

Enable the trend.

2

Force a true trigger condition.

Parameter Number

491

Parameter Type

Read/Write, Non–Linkable Sink

Display Units / Drive Units

None

Factory Default

0

Minimum Value

0

Maximum Value

2

File – Group

Diagnostics – Trend Setup

Enums

0 = Disable

1 = Enable

2 = Force Trig

492

Trend 4 Status

[Tr4 Status]

Tr4 Status identifies which state the trend is
currently in. The following states are possible:

1 Stopped

Trending is not executing.

2 Running

Trending is executing, but the trigger
point has not yet been reached.

3 Tripped/Trigger Trending is executing, and the trigger

point has been reached.

4 Tripped/Forced The trigger point was forced.

Parameter Number

492

Parameter Type

Read Only, Non–Linkable Source

Display Units / Drive Units

None

Factory Default

1

Minimum Value

1

Maximum Value

4

File – Group

Diagnostics – Trend I/O

Enums

1 = Stopped

2 = Running

3 = Trip Trig

4 = Force Trip