6–45
Parameters
Publication 1336 FORCE–5.18 ––March, 1999
489
Trend 4 Post Samples
[Tr4 Post Samples]
Tr4 Post Samples specifies the number of data
samples to be gathered once the trigger evaluation
becomes true. There is always a sample reserved
for the instance when the trigger condition becomes
true.
Parameter Number
489
Parameter Type
Read/Write, Non–Linkable Sink
Display Units / Drive Units
None
Factory Default
15
Minimum Value
0
Maximum Value
499
File – Group
Diagnostics – Trend Setup
490
Trend 4 Continuous Trigger
[Tr4 Cont Trigger]
Tr4 Cont Trigger specifies the type of trend. You can
choose either 0 for one–shot or 1 for continuous.
With a one–shot trend, once the trigger condition is
true and the number of samples after the trigger is
taken are gathered, the trend stops.
With a continuous trend, once the trigger condition is
true and the number of samples after the trigger is
taken are gathered, the trend continues looking for
the next occurrence of a true trigger condition.
Parameter Number
490
Parameter Type
Read/Write, Non–Linkable Sink
Display Units / Drive Units
None
Factory Default
0
Minimum Value
0
Maximum Value
1
File – Group
Diagnostics – Trend Setup
491
Trend 4 Select
[Tr4 Select]
Tr4 Select specifies the trend mode. The states are
as follows:
0
Disable the trend.
1
Enable the trend.
2
Force a true trigger condition.
Parameter Number
491
Parameter Type
Read/Write, Non–Linkable Sink
Display Units / Drive Units
None
Factory Default
0
Minimum Value
0
Maximum Value
2
File – Group
Diagnostics – Trend Setup
Enums
0 = Disable
1 = Enable
2 = Force Trig
492
Trend 4 Status
[Tr4 Status]
Tr4 Status identifies which state the trend is
currently in. The following states are possible:
1 Stopped
Trending is not executing.
2 Running
Trending is executing, but the trigger
point has not yet been reached.
3 Tripped/Trigger Trending is executing, and the trigger
point has been reached.
4 Tripped/Forced The trigger point was forced.
Parameter Number
492
Parameter Type
Read Only, Non–Linkable Source
Display Units / Drive Units
None
Factory Default
1
Minimum Value
1
Maximum Value
4
File – Group
Diagnostics – Trend I/O
Enums
1 = Stopped
2 = Running
3 = Trip Trig
4 = Force Trip