6–26
Parameters
Publication 1336 FORCE–5.18 ––March, 1999
387
Analog Output 1
[Analog Out 1]
Analog Out 1 converts a
±
32767 value to a
±
10V
signal. The digital value is linked to a 1336 FORCE
source parameter which provides a value that is
scaled and offset. The results are converted to a
voltage signal, where
±
2048 results in a
±
10V
output.
Parameter Number
387
Parameter Type
Read/Write, Sink
Display Units / Drive Units
±
32767
Factory Default
0
Minimum Value
–32767
Maximum Value
+32767
File – Group
Communication I/O – Analog Output
388
Analog Output 2
[Analog Out 2]
Analog Out 2 converts a
±
32767 value to a
±
10V
signal. The digital value is linked to a 1336 FORCE
source parameter which provides a value that is
scaled and offset. The results are converted to a
voltage signal, where
±
2048 results in a
±
10V
output.
Parameter Number
388
Parameter Type
Read/Write, Sink
Display Units / Drive Units
±
32767
Factory Default
0
Minimum Value
–32767
Maximum Value
+32767
File – Group
Communication I/O – Analog Output
389
Analog Output 3
[Analog Out 3]
Analog Out 3 converts a
±
32767 value to a
±
10V
signal. The digital value is linked to a 1336 FORCE
source parameter which provides a value that is
scaled and offset. The results are converted to a
voltage signal, where
±
2048 results in a
±
10V
output.
Parameter Number
389
Parameter Type
Read/Write, Sink
Display Units / Drive Units
±
32767
Factory Default
0
Minimum Value
–32767
Maximum Value
+32767
File – Group
Communication I/O – Analog Output
390
Analog Output 4
[Analog Out 4]
Analog Out 4 converts a
±
32767 value to a
±
10V
signal. The digital value is linked to a 1336 FORCE
source parameter which provides a value that is
scaled and offset. The results are converted to a
voltage signal, where
±
2048 results in a
±
10V
output.
Parameter Number
390
Parameter Type
Read/Write, Sink
Display Units / Drive Units
±
32767
Factory Default
0
Minimum Value
–32767
Maximum Value
+32767
File – Group
Communication I/O – Analog Output
391
SCANport Analog Select
[SP Analog Sel]
SP Analog Sel indicates which port (1 through 5) is
to receive the SCANport analog input value that
appears in parameter 338, SP Analog In.
Parameter Number
391
Parameter Type
Read/Write, Sink
Display Units / Drive Units
None
Factory Default
1
Minimum Value
1
Maximum Value
5
File – Group
Communications I/O – Analog Output
Enums
1 = Port 1
2 = Port 2
3 = Port 3
4 = Port 4
5 = Port 5