Rockwell Automation 1336T ControlNet Frn1.02 Rev 1.5 User Manual
Page 174

6–32
Parameters
Publication 1336 FORCE–5.18 ––March, 1999
413
Clear Fault Mask
[Clr Fault Mask]
Clr Fault Mask controls which ports can generate a
clear fault command.
Parameter Number
413
Parameter Type
Read/Write, Non–Linkable Sink
Display Units / Drive Units
Bits
Factory Default
0
Minimum Value
0
Maximum Value
0FE Hex
File – Group
Communications I/O – SCANport Masks
Enums
Bit 1 = Port 1
Bit 2 = Port 2
Bit 3 = Port 3
Bit 4 = Port 4
Bit 5 = Port 5
Bit 6 = Channel A Bit 7 = Channel B
414
Reset Drive Mask
[Reset Drive Mask]
Reset Drive Mask controls which ports can reset a
fault.
Parameter Number
414
Parameter Type
Read/Write, Non–Linkable Sink
Display Units / Drive Units
Bits
Factory Default
0
Minimum Value
0
Maximum Value
0FE Hex
File – Group
Communication I/O – SCANport Masks
Enums
Bit 1 = Port 1
Bit 2 = Port 2
Bit 3 = Port 3
Bit 4 = Port 4
Bit 5 = Port 5
Bit 6 = Channel A Bit 7 = Channel B
415
Local Mask
[Local Mask]
Local Mask controls which ports are allowed to take
exclusive control of drive logic commands except
Stop. (Stop is accepted from any device regardless
of who has control.) You can only take exclusive
local control while the drive is stopped.
Parameter Number
415
Parameter Type
Read/Write, Non–Linkable Sink
Display Units / Drive Units
Bits
Factory Default
0
Minimum Value
0
Maximum Value
0FE Hex
File – Group Communications I/O – SCANport Owners
Enums
Bit 1 = Port 1
Bit 2 = Port 2
Bit 3 = Port 3
Bit 4 = Port 4
Bit 5 = Port 5
Bit 6 = Channel A Bit 7 = Channel B
416
SCANport Default Reference
[SP Default Ref]
SP Default Ref defines the default reference to be
used when the drive is powered up. You can
change the value of this parameter, but the change
is only accessed when the drive is powered up.
Parameter Number
416
Parameter Type
Read/Write, Non–Linkable Sink
Display Units / Drive Units
None
Factory Default
2
Minimum Value
1
Maximum Value
7
File – Group
Velocity Torque – Velocity Ref
Enums
Bit 1 = Xref1
Bit 2 = Preset1
Bit 3 = Preset2
Bit 4 = Preset3
Bit 5 = Preset4 Bit 6 = Preset5
Bit 7 = Xref2