Rockwell Automation 1336T ControlNet Frn1.02 Rev 1.5 User Manual
Page 169
6–27
Parameters
Publication 1336 FORCE–5.18 ––March, 1999
392
Analog Input 1 Offset
[Analog In 1 Offset]
Analog In 1 Offset determines the offset applied to
the raw Analog In 1 values before the scale factor is
applied. This allows you to shift the range of the
analog input.
Parameter Number
392
Parameter Type
Read/Write, Non–Linkable Sink
Display Units / Drive Units
±
4096
Factory Default
0
Minimum Value
–20 Volts
Maximum Value
+20 Volts
File – Group
Communications I/O – Analog Input
393
Analog Input 1 Scale
[Analog In 1 Scale]
Analog In 1 Scale determines the scale factor or
gain for the Analog In 1 value. A +10V dc signal
applied to Analog In 1 at TB21 is converted to a
+2048 digital value used by the 1336 FORCE.
Before the digital value is displayed or transferred to
the drive, the scale factor is applied allowing an
effective digital range of
±
32767 (16 x 2048). The
absolute digital value is clamped at 32767.
Scale Factor
Drive Units
1
2048
2
4096
4
8192
16
32767
Parameter Number
393
Parameter Type
Read/Write, Non–Linkable Sink
Display Units / Drive Units
±
32767
Factory Default
+1
Minimum Value
–16
Maximum Value
+16
File – Group
Communications I/O – Analog Input
394
Analog Input 2 Offset
[Analog In 2 Offset]
Analog In 2 Offset determines the offset applied to
the raw Analog In 2 values before the scale factor is
applied. This allows you to shift the range of the
analog input.
Parameter Number
394
Parameter Type
Read/Write, Non–Linkable Sink
Display Units / Drive Units
±
4096
Factory Default
0
Minimum Value
–20 Volts
Maximum Value
+20 Volts
File – Group
Communications I/O – Analog Input
395
Analog Input 2 Scale
[Analog In 2 Scale]
Analog In 2 Scale determines the scale factor or
gain for the Analog In 2 value. A +10V dc signal
applied to Analog In 2 at TB21 is converted to a
+2048 digital value used by the 1336 FORCE.
Before the digital value is displayed or transferred to
the drive, the scale factor is applied allowing an
effective digital range of
±
32767 (16 x 2048). The
absolute digital value is clamped at 32767.
Scale Factor
Drive Units
1
2048
2
4096
4
8192
16
32767
Parameter Number
395
Parameter Type
Read/Write, Non–Linkable Sink
Display Units / Drive Units
±
32767
Factory Default
+1
Minimum Value
–16
Maximum Value
+16
File – Group
Communications I/O – Analog Input