Rockwell Automation 1336T ControlNet Frn1.02 Rev 1.5 User Manual
Page 155
6–13
Parameters
Publication 1336 FORCE–5.18 ––March, 1999
307
ICN Board Status
[ICN Status]
ICN Status displays the status of the ControlNet
Adapter Board. You can use this parameter to
determine if no fault occurred, or if a warning, soft
fault, or hard fault occurred.
Parameter Number
307
Parameter Type
Read Only, Source
Display Units / Drive Units
None
Factory Default
0
Minimum Value
0
Maximum Value
3
File – Group
Diagnostics – Info
Enums
0 = No Faults
1 = Drv Warning
2 = Drv Soft Flt
3 = Drv Hard Flt
309
Language Select
[Language Sel]
You can use Language Sel to choose the language
you want the ControlNet Adapter Board to use for
parameter and fault display text. Currently, only
English is available.
Parameter Number
309
Parameter Type
Read Only
Display Units / Drive Units
None
Factory Default
0
Minimum Value
0
Maximum Value
1
File – Group
Startup – Drive Data Group
Diagnostics – Info
Enums
0 = English
1 = Alternate Language (not currently available)
314
Data Input A1
[Data In A1]
Data In A1 contains the first image word from the
SCANport output image table.
Parameter Number
314
Parameter Type
Read Only, Source
Display Units / Drive Units
None
Factory Default
0
Minimum Value
–32767
Maximum Value
+32767
File – Group
Communications I/O – SCANport I/O
315
Data Input A2
[Data In A2]
Data In A2 contains the second image word from the
SCANport output image table.
Parameter Number
315
Parameter Type
Read Only, Source
Display Units / Drive Units
None
Factory Default
0
Minimum Value
–32767
Maximum Value
+32767
File – Group
Communications I/O – SCANport I/O
316
Data Input B1
[Data In B1]
Data In B1 contains the third image word from the
SCANport output image table.
Parameter Number
316
Parameter Type
Read Only, Source
Display Units / Drive Units
None
Factory Default
0
Minimum Value
–32767
Maximum Value
+32767
File – Group
Communications I/O – SCANport I/O
317
Data Input B2
[Data In B2]
Data In B2 contains the fourth image word from the
SCANport output image table.
Parameter Number
317
Parameter Type
Read Only, Source
Display Units / Drive Units
None
Factory Default
0
Minimum Value
–32767
Maximum Value
+32767
File – Group
Communications I/O – SCANport I/O