beautypg.com

Trend file, Plc block transfer instruction data, Trend parameter definition – Rockwell Automation 1336T ControlNet Frn1.02 Rev 1.5 User Manual

Page 122

background image

4–80

Using Unscheduled Messaging

Publication 1336 FORCE–5.18 ––March, 1999

The Trend Parameter Definition allows you to read the list of trend
parameter numbers from the database.

PLC Block Transfer Instruction Data

PLC Message Write instruction length:

3 words

PLC Message Read instruction length:

13 words

Header

Word 1

Header

Word 1

Header

Word 2

Header

Word 2

Header

Word 3

Trend Number

Message Structure

Header

Word 3

Trend Number

PLC Decimal Value

4102

PLC Decimal Value

4102 –– Message OK

–28666 –– Message Error

Message Length

3

Message Length

13

PLC Request –– PLC Message Write

Drive Response –– PLC Message Read

Data

Word 4

Data

Word 5

Data

Word 6

Post Samples

Trend Sample Size

Trend Status

Parameter Number

Parameter Number

Parameter Number

Data

Word 7

Data

Word 8

Data

Word 9

Mode

Sample Time Rate

Operator Data

Parameter Number

Parameter Number

Parameter Number

Data

Word 10

Data

Word 11

Data

Word 12

Sampling Input

Comparison B

Comparison A

Parameter Number

Parameter Number

Parameter Number

Data

Word 13

Trend Output

Parameter Number

Trend File