Rockwell Automation 1336T ControlNet Frn1.02 Rev 1.5 User Manual
Page 180
![background image](/manuals/578189/180/background.png)
6–38
Parameters
Publication 1336 FORCE–5.18 ––March, 1999
460
Trend 1 Continuous Trigger
[Tr1 Cont Trigger]
Tr1 Cont Trigger specifies the type of trend. You can
choose either 0 for one–shot or 1 for continuous.
With a one–shot trend, once the trigger condition is
true and the number of samples after the trigger is
taken are gathered, the trend stops.
With a continuous trend, once the trigger condition is
true and the number of samples after the trigger is
taken are gathered, the trend continues looking for
the next occurrence of a true trigger condition.
Parameter Number
460
Parameter Type
Read/Write, Non–Linkable Sink
Display Units / Drive Units
None
Factory Default
0
Minimum Value
0
Maximum Value
1
File – Group
Diagnostics – Trend Setup
461
Trend 1 Select
[Tr1 Select]
Tr1 Select specifies the trend mode. The states are
as follows:
0
Disable the trend.
1
Enable the trend.
2
Force a true trigger condition.
Parameter Number
461
Parameter Type
Read/Write, Non–Linkable Sink
Display Units / Drive Units
None
Factory Default
0
Minimum Value
0
Maximum Value
2
File – Group
Diagnostics – Trend Setup
Enums
0 = Disable
1 = Enable
2 = Force Trig
462
Trend 1 Status
[Tr1 Status]
Tr1 Status identifies which state the trend is
currently in. The following states are possible:
1 Stopped
Trending is not executing.
2 Running
Trending is executing, but the trigger
point has not yet been reached.
3 Tripped/Trigger Trending is executing, and the trigger
point has been reached.
4 Tripped/Forced The trigger point was forced.
Parameter Number
462
Parameter Type
Read Only, Non–Linkable Source
Display Units / Drive Units
None
Factory Default
1
Minimum Value
1
Maximum Value
4
File – Group
Diagnostics – Trend I/O
Enums
1 = Stopped
2 = Running
3 = Trip Trig
4 = Force Trip
463
Trend Output 1
[Trend Out 1]
Trend Out 1 displays the latest 500 trend input data
values once the trigger condition is true and all post
samples are gathered. This parameter is updated at
the same rate as the data was sampled. This
parameter can be linked to Analog Output (for
example) and a chart recorder connected to Analog
Output to provide a hard copy of the trend data.
Parameter Number
463
Parameter Type
Read Only, Source
Display Units / Drive Units
None
Factory Default
0
Minimum Value
–32767
Maximum Value
+32767
File – Group
Diagnostics – Trend I/O