Rockwell Automation 1336T ControlNet Frn1.02 Rev 1.5 User Manual
Page 177
6–35
Parameters
Publication 1336 FORCE–5.18 ––March, 1999
440
SCANport Fault Selection
[SP Fault Sel]
SP Fault Sel indicates which ports will cause a drive
soft fault on loss of communications.
Parameter Number
440
Parameter Type
Read/Write, Sink
Display Units / Drive Units
Bits
Factory Default
0011
1110
Minimum Value
0000
0000
Maximum Value
0011
1110
File – Group
Diagnostics – Fault Select/Status
Communications I/O – Fault Select/Status
Enums
Bit 7 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1
Enums
Fault
Port 1
SP Pt1 Timeout (Flt 26038)
Port 2
SP Pt2 Timeout (Flt 26039)
Port 3
SP Pt3 Timeout (Flt 26040)
Port 4
SP Pt4 Timeout (Flt 26041)
Port 5
SP Pt5 Timeout (Flt 26042)
SP Offline
441
SCANport Warning Selection
[SP Warn Sel]
SP Warn Sel indicates which ports will cause a drive
warning on loss of communications.
Parameter Number
441
Parameter Type
Read/Write Sink
Display Units / Drive Units
Bits
Factory Default
0011
1110
Minimum Value
0000
0000
Maximum Value
0011
1110
File – Group
Diagnostics – Fault Select/Status
Communications I/O – Fault Select/Status
Enums
Bit 7 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1
Enums
Warning
Port 1
SP Pt1 Timeout (Flt 26038)
Port 2
SP Pt2 Timeout (Flt 26039)
Port 3
SP Pt3 Timeout (Flt 26040)
Port 4
SP Pt4 Timeout (Flt 26041)
Port 5
SP Pt5 Timeout (Flt 26042)
SP Offline
442
SCANport Fault Status
[SP Fault Sts]
SP Fault Sts indicates which communications soft
faults the drive has encountered at the ports.
Parameter Number
442
Parameter Type
Read Only, Source
Display Units / Drive Units
Bits
Factory Default
0011
1110
Minimum Value
0000
0000
Maximum Value
0011
1110
File – Group
Diagnostics – Fault Select/Status
Communications I/O – Fault Select/Status
Enums
Bit 7 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1
Enums
Fault
Port 1
SP Pt1 Timeout (Flt 26038)
Port 2
SP Pt2 Timeout (Flt 26039)
Port 3
SP Pt3 Timeout (Flt 26040)
Port 4
SP Pt4 Timeout (Flt 26041)
Port 5
SP Pt5 Timeout (Flt 26042)
SP Offline