Rockwell Automation 1336T ControlNet Frn1.02 Rev 1.5 User Manual
Page 134
5–7
Understanding the Resources of Your Drive
Publication 1336 FORCE–5.18 ––March, 1999
For each of these parameters, each bit represents a device:
If this bit is set:
Then, the owner is:
1
SCANport device 1
2
SCANport device 2
3
SCANport device 3
4
SCANport device 4
5
SCANport device 5
6
ChA Logic Cmd In
NOTE: Bit 0 is not used. Also, the SCANport device number is
determined by the SCANport connection it is plugged into.
Masking Control Functions
You can also mask control functions. This allows you to enable or
disable a control function for all or some of the devices.
Important: You cannot mask the stop command. Any device
attached to the ControlNet Adapter Board can stop the
drive at any time.
To set a mask for a control function, you can use the following
parameters:
To set a mask to control this function:
Use this
parameter:
Control which ports can accept the control functions
408
Issue forward/reverse commands
409
Issue a start command
410
Issue a jog command
411
Select an alternate reference or preset speed
412
Generate a clear fault command
413
Reset faults
414
Allow exclusive control of logic commands
415
For each of these parameters, each bit represents a device:
This bit:
Represents:
1
SCANport device 1
2
SCANport device 2
3
SCANport device 3
4
SCANport device 4
5
SCANport device 5
6
ChA Logic Cmd In
"