Basic Set Up

The Basic Set Up programming group provides a limited parameter
set, allowing quick start-up with minimal adjustment. If the user is
planning to implement some of the advanced features (e.g., Dual
Ramp, or Preset Slow Speed), then the Setup programming group
should be selected. It provides all the Basic Set Up parameter set plus
the advanced set.

Starting Mode must be programmed to Soft Start to obtain access to the Initial Torque parameter.

Starting Mode must be programmed to Current Limit to obtain access to the Current Limit Level
parameter.

Parameter

Option

SMC Option

Displays the type of controller. This is factory set and not adjustable.

Standard

Motor Connection

Displays the motor type to which the device is being connected.

Line or Delta

Line Voltage

Displays the system line voltage to which the unit is connected.

Starting Mode

Allows the user to program the SMC-Flex controller for the type of starting that best fits the application.

Soft Start, Current Limit, Full Voltage, Linear
Speed

Ramp Time

This sets the time period during which the controller will ramp the output voltage.

0…30 s

Initial Torque

The initial reduced voltage output level for the voltage ramp is established and adjusted with this parameter.

0…90% of locked rotor torque

Current Limit Level

The current limit level that is applied for the Ramp Time selected.

50…600% FLC

Kickstart Time

A boost current is provided to the motor for the programmed time period.

0.0…2.0 s

Kickstart Level

Adjusts the amount of current applied to the motor during kickstart.

0…90% of locked rotor torque

Stop Input

Allows the user to select the operation of terminal 18, Stop Input.

Coast, Stop Option

Option 1 Input

Allows the user to select the operation of terminal 16, Option Input #1.

Disable, Coast, Stop Option, Fault, Fault NC,
Network

Option 2 Input

Allows the user to select the operation of terminal 15, Option Input #2.

Disable, Slow Speed, Dual Ramp, Fault, Fault
NC, Network, Clear Fault

Stop Mode

Allows the user to program the SMC-Flex controller for the type of stopping that best fits the application.

Disable, Soft Stop, Linear Speed

Stop Time

This sets the time period which the controller will ramp the voltage during a stopping maneuver.

0.0…120 s

Overload Class

Disable, 10, 15, 20, 30

Service Factor

0.01…1.99

Motor FLC

1.0…2200

OL Reset

Auto, Manual

Aux1 Config

Contact is provided as standard with the SMC-Flex controller. This contact is located at terminals 19 and 20.
Aux Contacts 1 allows the user to configure the operation of the contacts.

Normal, Up-to-speed, Fault, Alarm, Network
Control, External Bypass: (N.O./N.C.)

Aux2 Config

Contact is provided as standard with the SMC-Flex controller. This contact is located at terminals 29 and 30.
Aux Contacts 2 allows the user to configure the operation of the contacts.

Normal, Up-to-speed, Fault, Alarm, Network
Control, External Bypass: (N.O./N.C.)

Aux3 Config

Contact is provided as standard with the SMC-Flex controller. This contact is located at terminals 31 and 32.
Aux Contacts 3 allows the user to configure the operation of the contacts.

Normal, Up-to-speed, Fault, Alarm, Network
Control, External Bypass: (N.O./N.C.)

Aux4 Config

Contact is provided as standard with the SMC-Flex controller. This contact is located at terminals 33 and 34.
Aux Contacts 4 allows the user to configure the operation of the contacts.

Normal, Up-to-speed, Fault, Alarm, Network
Control, External Bypass: (N.O./N.C.)

Parameter Mgmt

Recall of factory default parameter values.

Ready, Load Default