The Basic Set Up programming group provides a limited parameter
set, allowing quick start-up with minimal adjustment. If the user is
planning to implement some of the advanced features (e.g., Dual
Ramp, or Preset Slow Speed), then the Setup programming group
should be selected. It provides all the Basic Set Up parameter set plus
the advanced set.
➀
Starting Mode must be programmed to Soft Start to obtain access to the Initial Torque parameter.
➁
Starting Mode must be programmed to Current Limit to obtain access to the Current Limit Level
parameter.
Parameter
Option
SMC Option
Displays the type of controller. This is factory set and not adjustable.
Standard
Motor Connection
Displays the motor type to which the device is being connected.
Line or Delta
Line Voltage
Displays the system line voltage to which the unit is connected.
Starting Mode
Allows the user to program the SMC-Flex controller for the type of starting that best fits the application.
Soft Start, Current Limit, Full Voltage, Linear
Speed
Ramp Time
This sets the time period during which the controller will ramp the output voltage.
0…30 s
Initial Torque
➀
The initial reduced voltage output level for the voltage ramp is established and adjusted with this parameter.
0…90% of locked rotor torque
Current Limit Level
➁
The current limit level that is applied for the Ramp Time selected.
50…600% FLC
Kickstart Time
A boost current is provided to the motor for the programmed time period.
0.0…2.0 s
Kickstart Level
Adjusts the amount of current applied to the motor during kickstart.
0…90% of locked rotor torque
Stop Input
Allows the user to select the operation of terminal 18, Stop Input.
Coast, Stop Option
Option 1 Input
Allows the user to select the operation of terminal 16, Option Input #1.
Disable, Coast, Stop Option, Fault, Fault NC,
Network
Option 2 Input
Allows the user to select the operation of terminal 15, Option Input #2.
Disable, Slow Speed, Dual Ramp, Fault, Fault
NC, Network, Clear Fault
Stop Mode
Allows the user to program the SMC-Flex controller for the type of stopping that best fits the application.
Disable, Soft Stop, Linear Speed
Stop Time
This sets the time period which the controller will ramp the voltage during a stopping maneuver.
0.0…120 s
Overload Class
Disable, 10, 15, 20, 30
Service Factor
0.01…1.99
Motor FLC
1.0…2200
OL Reset
Auto, Manual
Aux1 Config
Contact is provided as standard with the SMC-Flex controller. This contact is located at terminals 19 and 20.
Aux Contacts 1 allows the user to configure the operation of the contacts.
Normal, Up-to-speed, Fault, Alarm, Network
Control, External Bypass: (N.O./N.C.)
Aux2 Config
Contact is provided as standard with the SMC-Flex controller. This contact is located at terminals 29 and 30.
Aux Contacts 2 allows the user to configure the operation of the contacts.
Normal, Up-to-speed, Fault, Alarm, Network
Control, External Bypass: (N.O./N.C.)
Aux3 Config
Contact is provided as standard with the SMC-Flex controller. This contact is located at terminals 31 and 32.
Aux Contacts 3 allows the user to configure the operation of the contacts.
Normal, Up-to-speed, Fault, Alarm, Network
Control, External Bypass: (N.O./N.C.)
Aux4 Config
Contact is provided as standard with the SMC-Flex controller. This contact is located at terminals 33 and 34.
Aux Contacts 4 allows the user to configure the operation of the contacts.
Normal, Up-to-speed, Fault, Alarm, Network
Control, External Bypass: (N.O./N.C.)
Parameter Mgmt
Recall of factory default parameter values.
Ready, Load Default