B-10

Parameter Information

Motor

Data

Motor ID

104

0…65535

0

Allows the user the ability to assign a specific
identification number to a motor and
controller combination. This can be useful for
network applications where you may need to
locate a specific motor/controller based on a
network address.

Motor

Data

CT Ratio

105

1…1500

Sets the proper current ratio when an external
current transformer is used for Medium
Voltage applications.

Motor

Data

MV Ratio

106

1…10000

Sets the proper feedback scaling when used
for Medium Voltage applications.

Basic Set

Up

Aux1 Config

107

Normal

Normal NC

Up To Speed

Up To Speed NC

Fault

Fault NC

Alarm

Alarm NC

Network

Network NC

External Bypass

Normal

Allows the user the ability to configure each
Auxiliary relay contact for a specific operation
Note: Normal = SMC in RUN

Basic Set

Up

Aux3 Config

108

Normal

Normal NC

Up To Speed

Up To Speed NC

Fault

Fault NC

Alarm

Alarm NC

Network

Network NC

External Bypass

Alarm

Allows the user the ability to configure each
Auxiliary relay contact for a specific operation
Note: Normal = SMC in RUN

Basic Set

Up

Aux4 Config

109

Normal

Normal NC

Up To Speed

Up To Speed NC

Fault

Fault NC

Alarm

Alarm NC

Network

Network NC

External Bypass

Normal

Allows the user the ability to configure each
Auxiliary relay contact for a specific operation
Note: Normal = SMC in RUN

Table B.1 Parameter List (Continued)

Group

Parameter

Name

Parameter

Number

Units

Min./

Max.

Default

Settings

Parameter Description

User

Settings