Parameter Information

B-7

Under-

voltage

Undervolt A Lvl

57

%V

0…99

0

Allows the user to set a voltage (% of line
Voltage) that will cause an Alarm when the
voltage falls below this value. A zero value is
the “off” setting.

Under-

voltage

Undervolt A Dly

58

Secs

0…99

0

Allows the user the ability to prevent some
nuisance Alarms by entering a delay period
that provides a window that the voltage
condition must persist within for the controller
to Alarm.

Over-

voltage

Overvolt F Lvl

59

%V

0…199

0

Allows the user to set a voltage (% of line
Voltage) that will cause a fault when the
voltage falls above this value. A zero value is
the “off” setting.

Over-

voltage

Overvolt F Dly

60

Secs

0…99

0

Allows the user the ability to prevent some
nuisance faults by entering a delay period that
provides a window that the voltage condition
must persist within for the controller to fault.

Over-

voltage

Overvolt A Lvl

61

%V

0…199

0

Allows the user to set a voltage (% of line
Voltage) that will cause an Alarm when the
voltage falls above this value. A zero value is
the “off” setting.

Over-

voltage

Overvolt A Dly

62

Secs

0…99

0

Allows the user the ability to prevent some
nuisance Alarms by entering a delay period
that provides a window that the voltage
condition must persist within for the controller
to Alarm.

Unbalance Unbalance F Lvl

63

%V

0…25

0

Allows the user to set a percentage of line to
line Voltages that will cause a fault when the
voltage falls above this value. A zero value is
the “off” setting.

Unbalance Unbalance F Dly

64

Secs

0…99

0

Allows the user the ability to prevent some
nuisance faults by entering a delay period that
provides a window that the voltage unbalance
condition must persist within for the controller
to fault.

Unbalance Unbalance A Lvl

65

%V

0…25

0

Allows the user to set a percentage of line to
line Voltages that will cause an Alarm when
the voltage falls above this value. A zero value
is the “off” setting.

Unbalance Unbalance A Dly

66

Secs

0…99

0

Allows the user the ability to prevent some
nuisance Alarms by entering a delay period
that provides a window that the voltage
unbalance condition must persist within for
the controller to Alarm.

Jam

Jam F Lvl

67

%FLC

0…1000

0

Allows the user to set an instantaneous over
current level (% of line FLC) that will cause a
fault. A zero value is the “off” setting.

Jam

Jam F Dly

68

Secs

0…99

0

Allows the user the ability to prevent some
nuisance faults by entering a delay period that
provides a window that the motor over current
condition must persist within for the controller
to fault.

Table B.1 Parameter List (Continued)

Group

Parameter

Name

Parameter

Number

Units

Min./

Max.

Default

Settings

Parameter Description

User

Settings