Troubleshooting
9-5
Table 9.D Motor Stops While Running
Table 9.E
Miscellaneous Situations
Starting
•
Mechanical problems
•
Inadequate Current
Limit setting
•
Failed control module
•
Check for binding or
external loading and
correct
•
Check motor
•
Adjust the Current Limit
Level to a higher setting
•
Replace control module
Display
Possible Cause
Possible Solutions
Fault displayed
•
See fault description
•
See Table 10.A
addressing fault
conditions
Display is blank
•
Control voltage is
absent
•
Failed control module
•
Check control wiring and
correct if necessary
•
Replace control module
Stopped
0.0 Amps
•
Pilot devices
•
Failed control module
•
Check control wiring and
correct if necessary
•
Replace control module
Starting
•
Two or three power
phases are missing
•
Failed control module
•
Check power system
•
Replace control module
Situation
Possible Cause
Possible Solutions
Motor current and
voltage fluctuates
with steady load
•
Motor
•
Erratic Load
•
Verify type of motor as a standard
squirrel cage induction motor
•
Check load conditions
Erratic operation
•
Loose
connections
•
Shut off all power to controller and
check for loose connections
Accelerates too fast
•
Starting time
•
Initial torque
•
Current limit
setting
•
Kickstart
•
Increase starting time
•
Lower initial torque setting
•
Decrease current limit setting
•
Lower kickstart time or turn off
Accelerates too
slow
•
Starting time
•
Initial torque
•
Current limit
setting
•
Kickstart
•
Decrease starting time
•
Increase initial torque setting
•
Increase current limit setting
•
Increase kickstart time or turn off
Fan does not
operate
•
Wiring
•
Failed fan(s)
•
Check wiring and correct if
necessary
•
Replace fan module
Motor stops too
quickly with
Soft Stop option
•
Time setting
•
Verify the programmed stopping
time and correct if necessary