Appendix

B

Parameter Information

Table B.1 Parameter List

Group

Parameter

Name

Parameter

Number

Units

Min./

Max.

Default

Settings

Parameter Description

User

Settings

Metering

Volts Phase A-B

1

Volt

Provides the three phase-to-phase supply
voltage measurements at all times, including
bypass operation.

Metering

Volts Phase B-C

2

Volt

Provides the three phase-to-phase supply
voltage measurements at all times, including
bypass operation.

Metering

Volts Phase C-A

3

Volt

Provides the three phase-to-phase supply
voltage measurements at all times, including
bypass operation.

Metering

Current Phase A

4

Amps

Provides the three phase motor current
measurement. This measurement is always
line current regardless of the motor
connection (Wye or Delta).

Metering

Current Phase B

5

Amps

Provides the three phase motor current
measurement. This measurement is always
line current regardless of the motor
connection (Wye or Delta).

Metering

Current Phase C

6

Amps

Provides the three phase motor current
measurement. This measurement is always
line current regardless of the motor
connection (Wye or Delta).

Metering

Watt Meter

7

KW/MW

Provides the power usage of the connected
motor. This value is calculated from the
voltage, current and power factor
measurements.

Metering

Kilowatt Hours

8

KWH/MWH

Provides the power usage over time of the
connected motor.

Metering

Elapsed Time

9

Hours

Indicates the total time of motor operation in
hours. The accumulated time is updated
continuously during run time.

Metering

Meter Reset

10

NO

ETM Reset

KWH Reset

NO

Provides the user the capability to reset the
value stored in the elapsed time (9) and
kilowatt hours (8) meters to zero.

Metering

Power Factor

11

0.00…0.99

Provides the operational displacement power
factor measurement of the connected motor.

Metering

Mtr Therm

Usage

12

%MTU

0…100

Provides the theoretical model of motor
heating as a percentage value. At 100% MTU,
the controller will fault on overload. This
model is based on the motor thermal overload
calculation.

Metering

Motor Speed

13

%

0…100

Indicates the operating percentage of motor
base speed when linear ramp is selected and
an external tachometer is used.