Parameter information, Appendix – Rockwell Automation 150 SMC-Flex User Manual User Manual
Page 135
![background image](/manuals/578005/135/background.png)
Appendix
B
Parameter Information
Table B.1 Parameter List
Group
Parameter
Name
Parameter
Number
Units
Min./
Max.
Default
Settings
Parameter Description
User
Settings
Metering
Volts Phase A-B
1
Volt
Provides the three phase-to-phase supply
voltage measurements at all times, including
bypass operation.
Metering
Volts Phase B-C
2
Volt
Provides the three phase-to-phase supply
voltage measurements at all times, including
bypass operation.
Metering
Volts Phase C-A
3
Volt
Provides the three phase-to-phase supply
voltage measurements at all times, including
bypass operation.
Metering
Current Phase A
4
Amps
Provides the three phase motor current
measurement. This measurement is always
line current regardless of the motor
connection (Wye or Delta).
Metering
Current Phase B
5
Amps
Provides the three phase motor current
measurement. This measurement is always
line current regardless of the motor
connection (Wye or Delta).
Metering
Current Phase C
6
Amps
Provides the three phase motor current
measurement. This measurement is always
line current regardless of the motor
connection (Wye or Delta).
Metering
Watt Meter
7
KW/MW
Provides the power usage of the connected
motor. This value is calculated from the
voltage, current and power factor
measurements.
Metering
Kilowatt Hours
8
KWH/MWH
Provides the power usage over time of the
connected motor.
Metering
Elapsed Time
9
Hours
Indicates the total time of motor operation in
hours. The accumulated time is updated
continuously during run time.
Metering
Meter Reset
10
NO
ETM Reset
KWH Reset
NO
Provides the user the capability to reset the
value stored in the elapsed time (9) and
kilowatt hours (8) meters to zero.
Metering
Power Factor
11
0.00…0.99
Provides the operational displacement power
factor measurement of the connected motor.
Metering
Mtr Therm
Usage
12
%MTU
0…100
Provides the theoretical model of motor
heating as a percentage value. At 100% MTU,
the controller will fault on overload. This
model is based on the motor thermal overload
calculation.
Metering
Motor Speed
13
%
0…100
Indicates the operating percentage of motor
base speed when linear ramp is selected and
an external tachometer is used.