Communications

7-5

To enable motor control from a connected human interface module or
communication module, you must take the following programming
steps:

1. Disconnect the HIM and allow to power down.

2. Reconnect the HIM. On Initializing screen, the bottom right cor-

ner of LCD shows Port X. Note this port number.

3. Go to Logic Mask, found as follows:

Main Menu: Parameter/Communications/Comm Mask/Logic
Mask

4. Set b0X equal to 1 (where X is the port number noted in step 2).

Important: The Logic Mask must be set to 0 prior to disconnecting

a human interface module from the SMC-FLEX
controller. If not, the unit will fault on a “Coms Loss”.