Parameter Information

B-9

Restart

Restart Attempts

82

0…5

0

Allows the user to enable the SMC-Flex to
auto-restart for up-to 5 attempts, other than
an SCR overtemp or motor overload fault. The
start signal must remain active for a restart to
occur.

Restart

Restart Delay

83

Secs

0…60

0

Provides a delay time between restart
attempts to allow for the condition to be
removed.

Linear List

Line Fault

Disable

84

0=Disable

1=Disable F1

2=DisableF41

3=Enable

Enable

This parameter gives the user the ability to
selectively disable specific fault codes such
as F1, F2, F3 and F41, F42, F43. These faults
are used to detect problems with incoming
power and the detection of appropriate zero
crosses (F1) or the firing of the SCRs based on
the current and voltage characteristics
associated with the SCR turning off (F41).
These faults can only occur during starting or
stopping and are usually related to the
incoming power condition.

Linear List Emergency Run

85

0 = Disable

1=Enable

Disable

This parameter defeats all running faults and
is only effective in the “run” mode. It will not
override faults prior to starting (i.e. shorted
SCR). This parameter is reset to “off/disable”
when control power is recycled.

Linear List

Current Loss

86

0 = Disable

1=Enable

Enable

This parameter allows the user to override a
current loss fault. This is indicative of the
typical failure mode of a damaged CT.

Comm
Masks

Logic Mask

87

8-bit binary

0

Allows the user to enable or disable control
from various serial interface ports (DPI) with a
"0" setting. If a port is set to “1”, the port will
be allowed to control the SMC and will
produce a comm. fault if disconnected.

DataLinks

Data In A1

88

0

16 bit Datalink

DataLinks

Data In A2

89

0

16 bit Datalink

DataLinks

Data In B1

90

0

16 bit Datalink

DataLinks

Data In B2

91

0

16 bit Datalink

DataLinks

Data In C1

92

0

16 bit Datalink

DataLinks

Data In C2

93

0

16 bit Datalink

DataLinks

Data In D1

94

0

16 bit Datalink

DataLinks

Data In D2

95

0

16 bit Datalink

DataLinks

Data Out A1

96

0

16 bit Datalink

DataLinks

Data Out A2

97

0

16 bit Datalink

DataLinks

Data Out B1

98

0

16 bit Datalink

DataLinks

Data Out B2

99

0

16 bit Datalink

DataLinks

Data Out C1

100

0

16 bit Datalink

DataLinks

Data Out C2

101

0

16 bit Datalink

DataLinks

Data Out D1

102

0

16 bit Datalink

DataLinks

Data Out D2

103

0

16 bit Datalink

Table B.1 Parameter List (Continued)

Group

Parameter

Name

Parameter

Number

Units

Min./

Max.

Default

Settings

Parameter Description

User

Settings

This parameter is not viewable without entering a special password in Firmware versions 4.001 or earlier. Contact Rockwell Automation technical support if you have
Version 4.001 firmware or earlier and need to access this parameter.