Rockwell Automation 150 SMC-Flex User Manual User Manual
Page 143
![background image](/manuals/578005/143/background.png)
Parameter Information
B-9
Restart
Restart Attempts
82
0…5
0
Allows the user to enable the SMC-Flex to
auto-restart for up-to 5 attempts, other than
an SCR overtemp or motor overload fault. The
start signal must remain active for a restart to
occur.
Restart
Restart Delay
83
Secs
0…60
0
Provides a delay time between restart
attempts to allow for the condition to be
removed.
Linear List
Line Fault
Disable
84
➂
0=Disable
1=Disable F1
2=DisableF41
3=Enable
Enable
This parameter gives the user the ability to
selectively disable specific fault codes such
as F1, F2, F3 and F41, F42, F43. These faults
are used to detect problems with incoming
power and the detection of appropriate zero
crosses (F1) or the firing of the SCRs based on
the current and voltage characteristics
associated with the SCR turning off (F41).
These faults can only occur during starting or
stopping and are usually related to the
incoming power condition.
Linear List Emergency Run
85
➂
0 = Disable
1=Enable
Disable
This parameter defeats all running faults and
is only effective in the “run” mode. It will not
override faults prior to starting (i.e. shorted
SCR). This parameter is reset to “off/disable”
when control power is recycled.
Linear List
Current Loss
86
➂
0 = Disable
1=Enable
Enable
This parameter allows the user to override a
current loss fault. This is indicative of the
typical failure mode of a damaged CT.
Comm
Masks
Logic Mask
87
8-bit binary
0
Allows the user to enable or disable control
from various serial interface ports (DPI) with a
"0" setting. If a port is set to “1”, the port will
be allowed to control the SMC and will
produce a comm. fault if disconnected.
DataLinks
Data In A1
88
0
16 bit Datalink
DataLinks
Data In A2
89
0
16 bit Datalink
DataLinks
Data In B1
90
0
16 bit Datalink
DataLinks
Data In B2
91
0
16 bit Datalink
DataLinks
Data In C1
92
0
16 bit Datalink
DataLinks
Data In C2
93
0
16 bit Datalink
DataLinks
Data In D1
94
0
16 bit Datalink
DataLinks
Data In D2
95
0
16 bit Datalink
DataLinks
Data Out A1
96
0
16 bit Datalink
DataLinks
Data Out A2
97
0
16 bit Datalink
DataLinks
Data Out B1
98
0
16 bit Datalink
DataLinks
Data Out B2
99
0
16 bit Datalink
DataLinks
Data Out C1
100
0
16 bit Datalink
DataLinks
Data Out C2
101
0
16 bit Datalink
DataLinks
Data Out D1
102
0
16 bit Datalink
DataLinks
Data Out D2
103
0
16 bit Datalink
Table B.1 Parameter List (Continued)
Group
Parameter
Name
Parameter
Number
Units
Min./
Max.
Default
Settings
Parameter Description
User
Settings
➂
This parameter is not viewable without entering a special password in Firmware versions 4.001 or earlier. Contact Rockwell Automation technical support if you have
Version 4.001 firmware or earlier and need to access this parameter.