Smc — flex bit identification – Rockwell Automation 150 SMC-Flex User Manual User Manual

Page 112

background image

7-8

Communications

SMC — Flex Bit Identification

Table 7.G Logic Status Word

Bit #

Status

Description

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

X

Enabled

1 — Control Power Applied
0 — No Control Power

X

Running

1 — Power Applied to Motor
0 — Power not Applied to Motor

X

Phasing

1 — ABC Phasing
0 — CBA Phasing

X

Phasing
Active

1 — 3-phase is valid
0 — No valid 3-phase detected

X

Starting
(Accel)

1 — Performing a Start Maneuver
0 — Not Performing a Start Maneuver

X

Stopping
(Decel)

1 — Performing a Stop Maneuver
0 — Not Performing a Stop Maneuver

X

Alarm

1 — Alarm Present
0 — No Alarm Present

X

Fault

1 — Fault Condition Exists
0 — No Fault Condition

X

At Speed

1 — Full Voltage Applied
0 — Not Full Voltage Applied

X

Start/
Isolation

1 — Start/Isolation Contactor Enabled
0 — Start/Isolation Contactor Disabled

X

Bypass

1 — External Bypass Contactor
Enabled
0 — External Bypass Contactor
Disabled

X

Ready

1 — Ready
0 — Not Ready

X

Option 1
Input

1 — Input Active
0 — Input Inactive

X

Option 2
Input

1 — Input Active
0 — Input Inactive

Bits 14 and 15 — Not Used