Rockwell Automation 150 SMC-Flex User Manual User Manual
Page 147
Parameter Information
B-13
Linear List
Fault 3
126
0…255
Fault buffer #3 represents fault history of the
device with fault #1 being the current fault
and fault #5 being the oldest fault kept in
memory.
Linear List
Fault 4
127
0…255
Fault buffer #4 represents fault history of the
device with fault #1 being the current fault
and fault #5 being the oldest fault kept in
memory.
Linear List
Fault 5
128
0…255
Fault buffer #5 represents fault history of the
device with fault #1 being the current fault
and fault #5 being the oldest fault kept in
memory.
Linear List
Ramp Time E
129
➂
Sec
0…999
0
This parameter provides the user with the
ability to extend the ramp time beyond the
initial range of 0-30 seconds. To use this
parameter, parameter 18 must be set to 0.
Linear List
Ramp Time 2E
130
➂
Sec
0…999
0
Allows for the second ramp time to also be
extended. To use this parameter, parameter
26 must be set to 0.
Linear List
Stop Time E
131
➂
Sec
0…999
0
Allows the stop time be extended beyond the
limit of 120 seconds. Parameter 33 must be
set to 0 for this parameter to be active.
Basic Set
Up
Option Input 1
132
Disable
Coast
Stop Option
Fault
Fault NC
Network
Stop Option
Provides the user with the ability to define the
function of option Input #1.
Basic Set
Up
Stop Input
133
Coast
Stop Option
Coast
Provides the user with the ability to define the
function of the stop input.
Linear List Elapsed Time 2
134
➂
Hours
0.0/3000.0
This is an additional Elapsed Time Meter that
cannot be reset by the user. It increments
exactly as the Elapsed Time but cannot be
reset.
Table B.1 Parameter List (Continued)
Group
Parameter
Name
Parameter
Number
Units
Min./
Max.
Default
Settings
Parameter Description
User
Settings
➂
This parameter is not viewable without entering a special password in Firmware versions 4.001 or earlier. Contact Rockwell Automation technical support if you have
Version 4.001 firmware or earlier and need to access this parameter.