beautypg.com

Rockwell Automation 150 SMC-Flex User Manual User Manual

Page 13

background image

Product Overview

1-5

Preset Slow Speed

This option can be used in applications that require a slow speed jog
for general purpose positioning. Preset Slow Speed provides either
7% of base speed (low) or 15% of base speed (high) settings in the
forward direction. Reverse can also be programmed and offers 10%
of base speed (low) and 20% of base speed (high) settings.

Figure 1.6 Preset Slow Speed

Start

Run

100%

Motor

Speed

Time (seconds)

15% - High

7% - Low

10% - Low

20% - High

Forward

Reverse

ATTENTION

!

Slow speed running is not intended for continuous
operation due to reduced motor cooling.