Rockwell Automation 20-COMM-D DeviceNet Adapter Series B FRN 2.xxx User Manual
Page 151
Using Explicit Messaging
6-23
20-COMM-D DeviceNet Adapter User Manual
Publication 20COMM-UM002G-EN-P
Table 6.L Example Scattered Read Request Data
Figure 6.25 Example Scattered Read Request Data File
Address
Value
Description
Hex.
(1)
(1)
In RSLogix 5 software, leading zeros are not displayed in data file addresses. For example, ‘0024’ in address
N30:1 is shown as ‘24’.
Dec.
N30:0
0101
257
TXID = 01, Command = 01 (execute)
N30:1
0024
36
Port = 00, Size = 36 bytes
(2)
(2)
The maximum number of bytes that can be entered is 120 (78 Hex.), which represents 19 parameters. The
number of required bytes always includes 2 for the Class, 2 for the Instance, 2 for the Attribute, 2 for each
parameter being read, and 4 for each parameter value (2 bytes for the Least SIgnificant Word and 2 bytes for the
Most Significant Word). For this example where 5 parameters are being read, a value of 36 bytes is required.
N30:2
4B01
19201
Service = 4B (Get_Attribute_Single), Address = 01 (Node)
N30:3
0093
147
Class = 93 (DPI Parameter Object)
N30:4
0000
0
Instance = Class Attributes (drive)
N30:5
0000
0
Attribute = 0 (Parameter Value)
N30:6
0001
1
Parameter Number Read = 1 [Output Freq]
N30:7
0000
0
Pad Word = 0 (always zero)
N30:8
0000
0
Pad Word = 0 (always zero)
N30:9
0003
3
Parameter Number Read = 3 [Output Current]
N30:10
0000
0
Pad Word = 0 (always zero)
N30:11
0000
0
Pad Word = 0 (always zero)
N30:12
0006
6
Parameter Number Read = 6 [Output Voltage]
N30:13
0000
0
Pad Word = 0 (always zero)
N30:14
0000
0
Pad Word = 0 (always zero)
N30:15
000C
12
Parameter Number Read = 12 [DC Bus Current]
N30:16
0000
0
Pad Word = 0 (always zero)
N30:17
0000
0
Pad Word = 0 (always zero)
N30:18
0011
17
Parameter Number Read = 17 [Analog In2 Value]
N30:19
0000
0
Pad Word = 0 (always zero)
N30:20
0000
0
Pad Word = 0 (always zero)