Rockwell Automation 5730 DriveLogix5730 Controller for PowerFlex 700S Drives with Phase II Control User Manual
Page 89
Configuring DriveLogix Motion
4-19
Make the parameter settings shown in the table below:
Table 4.B Parameter Settings for DriveLogix Motion Configuration
8.Type the desired value.
ahw0829.ti
f
Parameter
Value
Description
13 [Spd Ref2 Multi]
1
Speed Ref 2 scale value
24 [Spd Trim 3 Scale]
0.003
Speed Trim 3 scale value
27 [Speed Ref A Sel]
2
Select Speed Ref 2 as the speed reference
146 [FW TaskTime Sel]
(1)
(1)
Changes to these parameters require a drive reset before the changes will take effect. The HIM will indicate
“Reset Req’d” on the status line.
0
Firmware Task Time Selection.
147 [FW Functions En]
16 = 1
Position Control enabled
151 [Logic Command]
Bit 0 = 1
Bit10 = 1
Bit13 = 1
Bit 0 bypasses the speed ramp in the drive
Bit 10 enables Inertia Comp
Bit 13 enables the position loop within the drive.
222 [Motor Fdbk Sel Pri]
0 - 6
Select the Motor Speed Feedback being used. This is also
the feedback for the Servo Axis in DriveLogix Motion Group
600 [Lgx Comm Format]
19
This selects the format of the commands coming from
DriveLogix
686 [Motn Config]
Bits 0 - 2 Bit 0 = Change the polarity of the feedback only feedback
axis
Bit 1 = Enable Software Overtravel Limits
Bit 2 = Enable Hardware Overtravel Limits
701 [FdbkAxis FdbkSel]
1 – 10
This selects the feedback channel used for the “Feedback
Only axis” in the Motion Group in DriveLogix.
Encoders, Optional Feedback, and SynchLink selections.
See User Manual for details.
740 [Position Control]
Bit 1 = 1
Bit 6 = 0
Bit 2 = 1
Bit 8 = 0
This sets the position regulator to work with the DriveLogix
configuration and enables the Integral part of the regulator
742 [Position Ref Sel]
0
This configures the drive position loop to receive position
commands from DriveLogix via the Interpolator
824 [Local I/O Status]
Bit 0 = 0
Bit 1 = 1
Eliminate erroneous physical axis faults
904 [SL Node Cnfg]
Bit 0 =1
This sets up the SynchLink as the time keeper. This is used
to synchronize the Drive and DriveLogix.