A-6
DriveLogix5730 Controller Specifications
Embedded EtherNet/IP
Option LEDs
Module Status (MS) indicator
!
ATTENTION: The Embedded EtherNet/IP Option LEDs are
only operational when the drive is energized, and only visible
with the drive door open. Servicing energized equipment can be
hazardous. Severe injury or death can result from electrical
shock, burn or unintended actuation of controlled equipment.
Follow Safety related practices of NFPA 70E, ELECTRICAL
SAFETY FOR EMPLOYEE WORKPLACES. DO NOT work
alone on energized equipment!
ahw0
864.e
ps
Module Status (MS)
Link Status (LNK)
Network Status (NS)
Condition:
Status:
Indicates:
Recommended Action:
off
no power
The controller does not have power.
Check the controller power supply.
flashing green
standby
The port does not have an IP address and is
operating in BOOTP mode.
Verify that the BOOTP server is running.
solid green
OK
The port is operating correctly.
Normal operation. No action required.