Communicating with Devices on a ControlNet Link
Example 3: Total Connections Required by DriveLogix1
The following table calculates the connections used in this example.
If you configured the local I/O modules as rack-optimized, you would only
need the DIN-rail connection to the I/O modules, reducing the above
example by 3 connections.
You can configure the 1756-CNB module to use no connection. This is
useful if you configure all direct connections to their associated I/O
modules and do not need a rack-optimized connection.
Connection:
Amount:
DriveLogix1 controller to 3 local I/O modules
rack-optimized connection for the DIN rail
direct connection for each I/O module
1
3
DriveLogix1 controller to local 1788-CNC
0
DriveLogix1 controller to remote 1756-CNB
1
DriveLogix1 controller to remote ControlNet PLC-5
1
connected, cached MSG from DriveLogix1 to Control1
1
connected, cached MSG from DriveLogix1 to PLC5C1
1
Produced TagA
produced from DriveLogix1 to DriveLogix2
consumed by PLC5C1
1
1
Consumed TagB from DriveLogix2
1
Consumed INT from PLC5C1
1
total connections used: 12