Rockwell Automation 5730 DriveLogix5730 Controller for PowerFlex 700S Drives with Phase II Control User Manual
Page 66

3-16
Placing and Configuring Local I/O
The display for the fault data defaults to decimal. Change it to Hex to read
the fault code.
If the module faults, but the connection to the controller remains open, the
controller tags database displays the fault value 16#0E01_0001. The fault
word uses this format:
Where:
You can also view module fault data on the Connection tab of the Module
Properties screen.
See your 1769 module’s user documentation for a description of module
faults. To recover from module faults, correct the module fault condition
and send new data to the module by downloading the user program with
configuration data, inhibiting and then uninhibiting the module, or cycling
power.
23
15
7
0
27
19
11
3
}
31
Fault_Code_Value
FaultInfo
FaultCode
reserved
reserved
Connection_Closed
Fault_Bit
0 = connection open
1 = connection closed
fault_w
ord.eps
Bit
Description
Fault_Bit
This bit indicates that at least one bit in the fault word is set (1). If all the bits in the fault word are
cleared (0), this bit is cleared (0).
Connection_Closed
This bit indicates whether the connection to the module is open (0) or closed (1). If the connection
is closed (1), the Fault_Bit it set (1).
ahw0817.ti
f