Example 3: drivelogix controller to other devices – Rockwell Automation 5730 DriveLogix5730 Controller for PowerFlex 700S Drives with Phase II Control User Manual
Page 162
7-22
Communicating with Devices on a ControlNet Link
Each produced tags requires one connection for the producing controller
and an additional connection for each consuming controller. Each
consumed tag requires one connection.
Example 2: Total connections required by DriveLogix1
The following table calculates the connections used in this example.
If you configured the local I/O modules as rack-optimized, you would only
need the DIN-rail connection to the I/O modules, reducing the above
example by 3 connections.
Example 3: DriveLogix
Controller to Other Devices
In the following example, one DriveLogix controller communicates with a
Logix5550 controller and a ControlNet PLC-5 controller over ControlNet.
Connection:
Amount:
DriveLogix1 controller to 3 local I/O modules
rack-optimized connection for the DIN rail
direct connection for each I/O module
1
3
DriveLogix1 controller to local 1788-CNC
0
DriveLogix1 controller to remote 1788-CNC
0
connected, cached MSG from DriveLogix1 to DriveLogix2
1
produced tagA
produced from DriveLogix1 to DriveLogix2
other consumer (2 are configured)
1
1
produced tagA
produced from DriveLogix1 to DriveLogix2
other consumer (2 are configured)
1
1
consumed TagB
1
total connections used: 10
ahw0936
.eps
DriveLogix5730 Controller
(DriveLogix2)
ControlNet
DriveLogix5730 Controller
(DriveLogix1)
ControlLogix Controller
(Control1)
ControlNet PLC5
Controller
(PLC5C1)