Replacing the Battery
1. Open the drive door and connect to the appropriate communication port
on the controller while the drive and the DriveLogix5730 controller are
energized.
2. Upload the controller’s memory and program to a computer with
RSLogix 5000 programming software.
3. Remove power from the drive and the DriveLogix5730 controller. Verify
that the voltage on the bus capacitors has discharged before performing
any work on the drive. Measure the DC bus voltage at the +DC & –DC
terminals of the Power Terminal Block. The voltage must be zero.
4. Remove control cassette.
5. Does the existing battery show signs of leakage or damage?
6. Remove the old battery, by unplugging the battery and opening the clip
which secures the battery.
7. Install a new 1769-BA battery, by plugging the battery lead into the
socket.
8. Attach the battery label. Write on the battery label the date you install the
battery.
9. Secure the new battery in the battery clip.
10.Re-install the control cassette.
11.Energize the drive and the DriveLogix5730 controller.
!
ATTENTION: Servicing energized equipment can be
hazardous. Severe injury or death can result from electrical
shock, burn or unintended actuation of controlled equipment.
Follow Safety related practices of NFPA 70E, ELECTRICAL
SAFETY FOR EMPLOYEE WORKPLACES. DO NOT work
alone on energized equipment!
!
ATTENTION: The controller uses a lithium battery, which
contains potentially dangerous chemicals. Before handling or
disposing a battery, review Guidelines for Handling Lithium
Batteries, publication AG-5.4.
If:
Then:
Yes
Before handling the battery, review Guidelines for Handling Lithium Batteries,
publication AG-5.4.
No
Go to the next step.
!
ATTENTION: Only install a 1769-BA battery. If you install