Rockwell Automation 5730 DriveLogix5730 Controller for PowerFlex 700S Drives with Phase II Control User Manual
Page 192
A-4
DriveLogix5730 Controller Specifications
Indicator:
Color:
Description:
RUN
off
The controller is in Program or Test mode.
solid green
The controller is in Run mode.
FORCE
off
No tags contain I/O force values.
I/O forces are inactive (disabled).
solid amber
I/O forces are active (enabled).
I/O force values may or may not exist.
flashing amber
One or more input or output addresses have been forced to an On or Off
state, but the forces have not been enabled.
BAT
off
The battery supports memory.
solid red
Either the battery is:
not installed.
95% discharged and should be replaced.
I/O
off
Either:
There are no devices in the I/O configuration of the controller.
The controller does not contain a project (controller memory is empty).
solid green
The controller is communicating with all the devices in its I/O configuration.
flashing green
One or more devices in the I/O configuration of the controller are not
responding.
flashing red
The controller is not communicating to any devices.
The controller is faulted.
COM
off
No RS-232 activity.
flashing green
RS-232 activity.
OK
off
No power is applied.
flashing red
If the controller is:
a new controller
not a new controller
Then:
the controller requires a firmware update
A major fault occurred.
To clear the fault, either:
- Turn the key switch from PROG to RUN to PROG
- Go online with RSLogix 5000 software
solid red
The controller detected a non-recoverable fault, so it cleared the project
from memory. To recover:
Cycle power to the chassis.
Download the project.
Change to Run mode.
If the OK LED remains solid red, contact your Rockwell Automation
representative or local distributor.
solid green
Controller is OK.
flashing green
The controller is storing or loading a project to or from nonvolatile memory.