beautypg.com

Rockwell Automation 20L PowerFlex 700L Frame 1X Liquid-Cooled Adjustable Frequency AC Drive User Manual

Page 57

background image

PowerFlex 700L Frame 1X Drive Installation Instructions – Publication 20L-IN013A-EN-P – June 2009

57

Heat Dissipation

Table 14 Watts Loss @ Rated Load, Speed, and PWM Carrier Frequency

Control
(continued)

Speed Control:

Speed Regulation - without feedback (Vector
Control Mode)

0.1% of base speed across 120:1 speed range
120:1 operating range
50 rad/sec bandwidth

Speed Regulation - with feedback (Vector Control
Mode)

0.001% of base speed across 120:1 speed range
1000:1 operating range
250 rad/sec bandwidth

Torque Regulation:

Torque regulation without Feedback;

±

5%, 600 rad/sec bandwidth

Torque regulation with Feedback;

±

2%, 2500 rad/sec bandwidth

Selectable Motor Control:

Sensorless Vector with full tuning. Standard V/Hz
with full custom capability and Vector Control with
Force Technology (with and without feedback).

Stop Modes

Multiple programmable stop modes including
Ramp, Coast, DC-Brake, Ramp-to-Hold, and
S-curve.

Accel/Decel

Two independently programmable accel and decel
times. Each time may be programmed from 0-3600
seconds in 0.1 second increments.

Liquid
Coolant

Coolant Type:

50% water / 50% propylene glycol

Max. Particle Size in Coolant:

5 microns

Minimum Flow Rate:

7.57 LPM (2 GPM)

Nominal Flow Rate:

9.46 LPM (2.5 GPM)

Maximum Flow Rate:

22.71 LPM (6 GPM)

Pressure Drop:

< 0.34 bar at 9.46 LPM (5 psi at 2.5 GPM), 20 °C

Maximum Coolant Temperature: 60 °C (140 °F)
Maximum Inlet Pressure:

3.45 bar (50 psi)

Encoder

Type:

Incremental, dual channel

Supply:

12V, 250 mA. 12V, 10 mA minimum inputs isolated
with differential transmitter, 250 kHz maximum.

Quadrature:

90°, ± 27 degrees at 25 °C

Duty Cycle:

50%, ± 10%

Requirements:

Encoders must be line driver type, quadrature
(dual channel) or pulse (single channel), 8…15V
DC output, single-ended or differential, and
capable of supplying a minimum of 10 mA per
channel. Maximum input frequency is 250 kHz.
The Encoder Interface Board accepts 12V DC
square-wave with a minimum high state of 7.0V
DC (12 volt encoder). Maximum low state voltage
is 0.4V DC.

Dynamic
Brake
Resistor

Regen DC Bus Voltage (V

d

):

790 volts

Minimum Ohms, External Brake
Resistor

8.2 ohms

Voltage

PWM
Freq.

Watts Loss
Into Air

Into Liquid

Total

480V

4 kHz

200

1700

1900

Category