Rockwell Automation 20L PowerFlex 700L Frame 1X Liquid-Cooled Adjustable Frequency AC Drive User Manual

Page 28

background image

PowerFlex 700L Frame 1X Drive Installation Instructions – Publication 20L-IN013A-EN-P – June 2009

28

3-Wire Control
Internal supply

• No changes required if parameters

are at factory default settings

3-Wire Control
External supply (I/O Board
dependent). Requires 3-wire
functions only ([Digital In1
Sel]). Using 2-wire selections
will cause a type 2 alarm.

• No changes required if parameters

are at factory default settings

Digital Input
PLC Output Card (Board
dependent). Resistors are
recommended to dissipate
leakage current.

• No changes required if parameters

are at factory default settings

Digital Output
Relays shown in powered
state with drive faulted. See

Table 9

.

Vector Control:
2 relays at terminal 14…16

Standard Control:
1 relay at terminals 14…16

Vector Control:
• Select Source to Activate:

Parameters 380/384/388

Standard Control:
• Select Source to Activate:

Parameters 380/384

Enable Input

Vector Control
• Configure with Parameter 366.

For dedicated hardware Enable:
Remove Jumper J10 (see

page 30

)

Standard Control:
• Configure with Parameter 366

(1)

Refer to the Attention statements on

page 24

for important bipolar wiring information.

(2)

A PTC (Positive Temperature Coefficient) device (motor thermistor), embedded in the motor windings, can be
monitored by the drive for motor thermal protection.

(3)

Important: Programming inputs for 2 wire control (Run) deactivates all HIM Start buttons unless Parameter 192
[Save HIM Ref], bit 1 (Manual Mode) = “1.” This will allow the HIM to control Start and Jog.

Input/Output

Connection Example

Required Parameter Changes

Start

24
25
26
27
28

Stop

Start

25

27
28

Stop

115V/

+24V

Neutral/

Common

25

27
28

Control from
Prog. Controller

Neutral/

Common

10k Ohm, 2 Watt

Power Source

11
12
13
14
15
16

Fault
NOT Fault

NOT Run
Run

or

32