PowerFlex 700L Frame 1X Drive Installation Instructions – Publication 20L-IN013A-EN-P – June 2009
41
ALT Functions
To use an ALT function, start at the Main Menu and press the ALT key,
release it, then press the programming key associated with one of the
following functions:
The PowerFlex 700 start up routines allow the user to commission the drive
more quickly and accurately. If you have an LCD HIM, two methods are
provided.
•
S.M.A.R.T. Start
This routine is accessible by using the “ALT” function key on the LCD
HIM. This keystroke brings up a list of parameters needed to program
the eight most commonly adjusted drive functions. These include Start,
Stop, Minimum Speed, Maximum Speed, Acceleration Time,
Deceleration Time, Reference source (speed command) and Electronic
Overload setting for the motor. No knowledge of parameter organization
or access is required. S.M.A.R.T. Start can commission the drive in just a
few minutes. See
Running S.M.A.R.T. Start on page 43
•
Assisted Start Up
Three levels of Assisted Start Up (Basic, Detailed and Application) assist
the user in commissioning the drive by asking simple Yes/No or “Enter
Data” questions. The user is guided through the Start Up to reduce the
amount of time necessary to get the drive “up and running.” The
following are included in startup:
– Input Voltage Ratings
– Motor Data
– Motor Tests & Auto-tuning
ALT Key…then
Function
Function Description
S.M.A.R.T.
Displays the S.M.A.R.T. screen. This function allows the drive
parameter values to be quickly programed by directly accessing the
most frequently used drive functions. Refer to
for more information.
Log In/Out
Log in to change parameter settings.
Log out to protect parameter settings.
Change a password.
View
Allows the selection of how parameters will be viewed or detailed
information about a parameter or component.
Device
Select a connected adapter for editing.
Lang
Displays the language selection screen. The LCD Human Interface
Module (HIM) on an architecture class drive allows you to change
the display language any time.
Auto/Man
Switches between Auto and Manual Modes. If the Human Interface
Module (HIM) requests Manual Mode, the Speed Reference source
is transferred to the Human Interface Module (HIM).
Remove
Allows Human Interface Module (HIM) removal without causing a
fault if the Human Interface Module (HIM) is not the last controlling
device and does not have Manual control of the drive.
Param #
Allows entry of a parameter number for viewing/editing.
ALT
Esc
Esc
Esc
Sel
Sel
+/–
Start-Up Routines