Rockwell Automation 20L PowerFlex 700L Frame 1X Liquid-Cooled Adjustable Frequency AC Drive User Manual
Page 47
PowerFlex 700L Frame 1X Drive Installation Instructions – Publication 20L-IN013A-EN-P – June 2009
47
Alarm
No.
Ty
p
e
(1
)
(1)
See the PowerFlex 700 Series B User Manual for a description of alarm types.
Description
Dig In
ConflictA
17
➁
Digital input functions are in conflict. Combinations marked with a “ ” will
cause an alarm.
Dig In
ConflictB
18
➁
A digital Start input has been configured without a Stop input or other
functions are in conflict. Combinations that conflict are marked with a “ ” and
will cause an alarm.
Dig In
ConflictC
19
➁
More than one physical input has been configured to the same input function.
Multiple configurations are not allowed for the following input functions:
Forward/Reverse
Run Reverse
Bus Regulation Mode B
Speed Select 1
Jog Forward
Acc2 / Dec2
Speed Select 2
Jog Reverse
Accel 2
Speed Select 3
Run
Decel 2
Run Forward
Stop Mode B
TB Man Ref
Cflct
30
➁
Occurs when:
• “Auto/Manual” is selected (default) for Parameter 363 [Digital In3 Sel]
and
• Parameter 096 [TB Man Ref Sel] has been reprogrammed.
No other use for the selected analog input may be programmed.
Example: If Parameter 096 [TB Man Ref Sel] is reprogrammed to “2” (Analog
In 2), all of the factory default uses for Analog In 2 must be reprogrammed
(such as Parameters 90, 117, 128 and 179). Refer to the Auto/Manual
Examples section of the PowerFlex 700 Series B User Manual.
To correct:
• Verify/reprogram the parameters that reference an analog input
or
• Reprogram Parameter 363 [Digital In3 Sel] to another function or “0” (Not
Used).