I/o wiring examples – Rockwell Automation 20L PowerFlex 700L Frame 1X Liquid-Cooled Adjustable Frequency AC Drive User Manual
Page 27
PowerFlex 700L Frame 1X Drive Installation Instructions – Publication 20L-IN013A-EN-P – June 2009
27
I/O Wiring Examples
Input/Output
Connection Example
Required Parameter Changes
Potentiometer Unipolar
Speed Reference
(1)
10k Ohm Pot. Recommended
(2k Ohm Minimum)
• Adjust Scaling:
Parameters 91/92 and 325/326
• View Results: Parameter 002
Analog Input Bipolar
Speed Reference
±
10V Input
• Set Direction Mode:
Parameter 190 = “1” (Bipolar)
• Adjust Scaling:
Parameters 91/92 and 325/326
• View Results: Parameter 002
Analog Voltage Input
Unipolar Speed Reference
0…10V Input
• Configure Input with Parameter 320
• Adjust Scaling:
Parameters 91/92 and 325/326
• View results: Parameter 002
Analog Current Input
Unipolar Speed Reference
0…20 mA Input
• Configure Input for Current:
Parameter 320 and add jumper at
appropriate terminals
• Adjust Scaling:
Parameters 91/92 and 325/326
• View results: Parameter 002
Analog Current Input
Unipolar Speed Reference
4…20 mA Input
• Configure Input for Current:
Parameter 320, bit 1 = “Current”
• Adjust Scaling:
Parameters 91/92 and 325/326
• View Results: Parameter 002
Analog Input, PTC
PTC OT set > 5V
PTC OT cleared < 4V
PTC Short < 0.2V
• Set Fault Config 1:
Parameter 238, bit 7 = “Enabled”
• Set Alarm Config 1:
Parameter 259, bit 11 = “Enabled”
• View Status Drive Alarm 1:
Parameter 211, bit 11 = “True”
HW PTC Input
(2)
PTC OT set > 5V
PTC OT cleared < 4V
PTC Short < 0.2V
• Set Fault Config 1:
Parameter 238, bit 13 = “Enabled”
• Set Alarm Config 1:
Parameter 259, bit 18 = “Enabled”
• View Status: Drive Alarm 1:
Parameter 211, bit 18 = “True”
2-Wire Control
Non-Reversing
(3)
24V DC internal supply
• Disable Digital Input #1:
Parameter 361 = “0” (Not Used)
• Set Digital Input #2:
Parameter 362 = “7” (Run)
• Set Direction Mode:
Parameter 190 = “0” (Unipolar)
2-Wire Control
Reversing
External supply (I/O Board
dependent)
• Set Digital Input #1:
Parameter 361 = “8” (Run Forward)
• Set Digital Input #2:
Parameter 362 = “9” (Run Reverse)
3
4
5
22
3
4
Common
+
3
4
Common
+
Vector
3
4
19
20
Common
+
Standard
19
20
Common
+
Vector
5
3.32k
Ohm
1.8k
PTC
Ferrite
Bead
1
2
22
1.8k
PTC
Ferrite
Bead
10
23
24
25
26
28
Stop-Run
25
27
28
Run Rev.
Run Fwd.
115V/
+24V
Neutral/
Common