PowerFlex 700L Frame 1X Drive Installation Instructions – Publication 20L-IN013A-EN-P – June 2009

27

I/O Wiring Examples

Input/Output

Connection Example

Required Parameter Changes

Potentiometer Unipolar
Speed Reference

(1)

10k Ohm Pot. Recommended
(2k Ohm Minimum)

• Adjust Scaling:

Parameters 91/92 and 325/326

• View Results: Parameter 002

Analog Input Bipolar
Speed Reference

±

10V Input

• Set Direction Mode:

Parameter 190 = “1” (Bipolar)

• Adjust Scaling:

Parameters 91/92 and 325/326

• View Results: Parameter 002

Analog Voltage Input
Unipolar Speed Reference
0…10V Input

• Configure Input with Parameter 320
• Adjust Scaling:

Parameters 91/92 and 325/326

• View results: Parameter 002

Analog Current Input
Unipolar Speed Reference

0…20 mA Input

• Configure Input for Current:

Parameter 320 and add jumper at
appropriate terminals

• Adjust Scaling:

Parameters 91/92 and 325/326

• View results: Parameter 002

Analog Current Input
Unipolar Speed Reference

4…20 mA Input

• Configure Input for Current:

Parameter 320, bit 1 = “Current”

• Adjust Scaling:

Parameters 91/92 and 325/326

• View Results: Parameter 002

Analog Input, PTC

PTC OT set > 5V
PTC OT cleared < 4V
PTC Short < 0.2V

• Set Fault Config 1:

Parameter 238, bit 7 = “Enabled”

• Set Alarm Config 1:

Parameter 259, bit 11 = “Enabled”

• View Status Drive Alarm 1:

Parameter 211, bit 11 = “True”

HW PTC Input

(2)

PTC OT set > 5V
PTC OT cleared < 4V
PTC Short < 0.2V

• Set Fault Config 1:

Parameter 238, bit 13 = “Enabled”

• Set Alarm Config 1:

Parameter 259, bit 18 = “Enabled”

• View Status: Drive Alarm 1:

Parameter 211, bit 18 = “True”

2-Wire Control
Non-Reversing

(3)

24V DC internal supply

• Disable Digital Input #1:

Parameter 361 = “0” (Not Used)

• Set Digital Input #2:

Parameter 362 = “7” (Run)

• Set Direction Mode:

Parameter 190 = “0” (Unipolar)

2-Wire Control
Reversing

(3)

External supply (I/O Board
dependent)

• Set Digital Input #1:

Parameter 361 = “8” (Run Forward)

• Set Digital Input #2:

Parameter 362 = “9” (Run Reverse)

3
4
5

22

3
4

Common

+

3
4

Common

+

Vector

3
4

19
20

Common

+

Standard

19
20

Common

+

Vector

5

3.32k

Ohm

1.8k

PTC

Ferrite

Bead

1
2

22

1.8k

PTC

Ferrite

Bead

10

23

24
25
26

28

Stop-Run

25

27
28

Run Rev.

Run Fwd.

115V/

+24V

Neutral/

Common