Information about start-up motor tests – Rockwell Automation 20L PowerFlex 700L Frame 1X Liquid-Cooled Adjustable Frequency AC Drive User Manual
Page 38

PowerFlex 700L Frame 1X Drive Installation Instructions – Publication 20L-IN013A-EN-P – June 2009
38
❏ 7. Press the Enter key to display the Start-Up Menu.
❏ 8. Use the Arrow keys to highlight “2. Basic”.
❏ 9. Press the Enter key. Follow the menu using the Enter key which will step
you through the Start-Up routine.
The Basic Start-Up routine asks simple questions and prompts you to
input required information. See also
.
Control schemes vary based on which Start/Jog Source is selected in Step 3
(Motor Tests) of the HIM Basic Start-Up procedure described in Assisted
Start Up on
. The following table lists the Start/Jog Source for each
selection:
During motor tests and tuning procedures, the drive may modify certain
parameter values for proper Start Up operation. These values are then reset
to their original values when Start Up is complete. The affected parameters
are 053, 080, 276, 278, and 361…366. If power is removed from the drive
during the tests without aborting the auto-tune procedure, these parameters
may not reset to their original value. If this situation occurs, reset the drive
to factory defaults (see
Restoring Factory Defaults on page 45
the Start Up procedure.
Information About Start-Up Motor Tests
Start/Jog Source
Control Source Description
Digital Inputs
Digital In 1 = Stop; Digital In 2 = Start; Digital In 3 = Jog
Local Human Interface
Module (HIM) – Port 1
Human Interface Module (HIM) connected to DPI Port 1 controls Stop/
Start/Jog
Digital In 1…6 are temporarily disabled during motor tests.
Remote HIM
Human Interface Module (HIM) connected to DPI Port 2 controls Stop/
Start/Jog
Digital In 1…6 are temporarily disabled during motor tests.