PowerFlex 700L Frame 1X Drive Installation Instructions – Publication 20L-IN013A-EN-P – June 2009

17

Wire Recommendations

Type

Wire Type(s)

Description

Min. Insulation
Rating

Power

(1)(2)

Standard

600V, 90 °C (194 °F) XHHW2/RHW-2
Anixter B209500-B209507, Belden
29501-29507, or equivalent

• Four tinned copper conductors

with XLPE insulation.

• Copper braid/aluminum foil

combination shield and tinned
copper drain wire.

• PVC jacket.

Signal

(1)

(3)

(4)

Standard Analog I/O

Belden 8760/9460 (or equivalent)

0.750 mm

2

(18 AWG), twisted pair,

100% shield with drain.

300V,
75…90 °C
(167…194 °F)

Belden 8770 (or equivalent)

0.750 mm

2

(18 AWG), 3 conductor,

shielded for remote pot only.

Encoder/Pulse I/O:
<30 m (100 ft.)

Combined: Belden 9730

(5)

0.196 mm

2

(24 AWG)

Encoder/Pulse I/O:
30…152 m (100…500 ft.)

Signal: Belden 9730/9728

(5)

0.196 mm

2

(24 AWG)

Power: Belden 8790

(6)

0.750 mm

2

(18 AWG)

Combined: Belden 9892

(7)

0.330 mm

2

(18 AWG),

power is 0.500 mm

2

(20 AWG)

Encoder/Pulse I/O:
152…259 m (500…850 ft.)

Signal: Belden 9730/9728

(5)

0.196 mm

2

(24 AWG)

Power: Belden 8790

(6)

0.750 mm

2

(18 AWG)

Combined: Belden 9773/9774

(8)

0.750 mm

2

(18 AWG)

Digital I/O

(1)

(3)

(4)

Shielded

Multi-conductor shielded cable such
as Belden 8770 (or equivalent)

0.750 mm

2

(18 AWG),

3 conductor, shielded.

300V,
60 °C (140 °F)

(1)

Control and signal wires should be separated from power wires by at least 0.3 meters (1 foot).

(2)

The use of shielded wire for AC input power may not be necessary but is always recommended.

(3)

If the wires are short and contained within a cabinet which has no sensitive circuits, the use of shielded wire may not be necessary, but is always
recommended.

(4)

I/O terminals labeled “(–)” or “Common” are not referenced to earth ground and are designed to greatly reduce common mode interference.
Grounding these terminals can cause signal noise.

(5)

Belden 9730 is 3 individually shielded pairs (2 channel + power). If 3 channel is required, use Belden 9728.

(6)

Belden 8790 is 1 shielded pair.

(7)

Belden 9892 is 3 individually shielded pairs (3 channel) + 1 shielded pair for power.

(8)

Belden 9773 is 3 individually shielded pairs (2 channel + power). If 3 channel is required, use Belden 9774.