Ce conformity – Rockwell Automation 20L PowerFlex 700L Frame 1X Liquid-Cooled Adjustable Frequency AC Drive User Manual
Page 5
PowerFlex 700L Frame 1X Drive Installation Instructions – Publication 20L-IN013A-EN-P – June 2009
5
Compliance with the Low Voltage Directive and Electromagnetic
Compatibility Directive has been demonstrated using harmonized European
Norm (EN) standards published in the Official Journal of the European
Communities. PowerFlex 700L drives, including Frame 1X, comply with
the EN standards listed below when installed according to this PowerFlex
700L Frame 1X Liquid-Cooled Adjustable Frequency AC Drive Installation
Instructions.
CE Declarations of Conformity are available online at:
Low Voltage Directive (2006/95/EC)
•
EN 50178 Electronic equipment for use in power installations
EMC Directive (2004/108/EC)
•
EN 61800-3 Adjustable speed elecrical power drive systems – Part 3:
EMC product standard including specific test methods
General Considerations
•
For CE compliance, drives must satisfy installation requirements related
to both EN 50178 and EN 61800-3 provided in this document.
•
PowerFlex 700L AC Drives comply with the EMC requirements of EN
61800-3 when installed according to good EMC practices and the
instructions provided in this document. However, many factors can
influence the EMC compliance of an entire machine or installation, and
compliance of the drive itself does not ensure compliance of all
applications.
•
PowerFlex 700L drives are not intended to be used on public low-voltage
networks which supply domestic premises. Without additional
mitigation, radio frequency interference is expected if used on such a
network. The installer is responsible to take measures such as
supplementary line filters and enclosures to prevent interference, in
addition to the installation requirements of this document.
•
Requirements for supplementary mitigation related to specific high
frequency emission limits are provided in
Table 1
.
Table 1
PowerFlex 700L Frame 1X RF Emission Compliance and Installation
Requirements
CE Conformity
Standard / Limits
EN 61800-3 Cat. C1
EN 61000-6-3
CISPR11 Group 1 Class B
EN 61800-3 Cat. C2
EN 61000-6-4
CISPR11 Group 1 Class A
EN 61800-3 Cat. C3
I
≤
100 A Limits
Compliance possible with
supplementary mitigation
(Consult factory)
Compliance possible with
supplementary mitigation
(Consult factory)
Compliant without
supplementary EMC line filter
for motor cable
≤
5 m (16.4 ft)
More Stringent Limits
Less Stringent Limits