PowerFlex 700L Frame 1X Drive Installation Instructions – Publication 20L-IN013A-EN-P – June 2009
43
During a Start Up, the majority of applications require changes to only a
few parameters. The LCD HIM used with the drive offers S.M.A.R.T. start,
which displays the most commonly changed parameters. With these
parameters, you can set the following functions:
S - Start Mode and Stop Mode
M - Minimum and Maximum Speed
A - Accel Time 1 and Decel Time 1
R - Reference Source
T - Thermal Motor Overload
To run a S.M.A.R.T. start routine:
Important: This start-up routine requires an LCD HIM.
The Assisted start-up routine prompts you to input required information.
Access Assisted Start Up by selecting “Start Up” from the Main Menu.
To perform an Assisted Start-Up
Important: Done/Exit must be selected upon completion of the Start Up
routine in order for any Start Up/Autotune data to be saved.
Running S.M.A.R.T. Start
Step
Key(s)
Example LCD Displays
1. Press ALT and then Esc (S.M.A.R.T).
The S.M.A.R.T. start screen appears.
2. View and change parameter values as
desired. For more HIM information, see
Appendix B in the PowerFlex 700 Series
B User Manual (publication 20B-UM002).
3. Press Esc to exit the S.M.A.R.T. start.
ALT
Esc
Esc
F-> Stopped
Auto
0.0
Hz
Main Menu:
Diagnostics
Parameter
SMART List:
Digital In2 Sel
Stop Mode A
Minimum Speed
Running an Assisted Start Up
Step
Key(s)
Example LCD Displays
1. In the Main Menu, press the Up Arrow or
Down Arrow to scroll to “Start Up”.
2. Press Enter.
F-> Stopped
Auto
0.0
Hz
Main Menu:
Memory Storage
Start Up
Preferences